6.2 STATUS
b) SLOW EXCHANGE
PATH: ACTUAL VALUES
 SLOW EXCHANGE 1
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the slow EGD exchanges are displayed.
PATH: ACTUAL VALUES
 TELEPROT CH TESTS
The status information for two channels is shown here.
CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is "OK", teleprotection is
6
enabled and data is being received from the remote terminal; If the value is "FAIL", teleprotection enabled and data is
not being received from the remote terminal. If "n/a", teleprotection is disabled.
CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the

COMMANDS
CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
"FAIL" message will be displayed. The "N/A" value appears if the local relay ID is set to a default value of "0", the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
PATH: ACTUAL VALUES
 INCIPIENT FAULT 1
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the
6-10

STATUS
EGD PROTOCOL STATUS
SLOW EXCHANGE 1
SIGNATURE:
SLOW EXCHANGE 1
MESSAGE
DATA LENGTH:

STATUS
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
MESSAGE
PACKETS:
CHANNEL 2
MESSAGE
STATUS: n/a
CHANNEL 2 LOST
MESSAGE
PACKETS:
VALIDITY OF CHANNEL
MESSAGE
CONFIGURATION: FAIL
menu.

STATUS
INCIPIENT FAULT
INCIPIENT FAULT 1
PH A FAULTS: 0
INCIPIENT FAULT 1
MESSAGE
PH B FAULTS: 0
INCIPIENT FAULT 1
MESSAGE
PH C FAULTS: 0

COMMANDS
CLEAR RECORDS
F60 Feeder Protection System

PRODUCER STATUS
0
0

6.2.19 TELEPROTECTION CHANNEL TESTS

Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
INCIPIENT FAULT 1(2)
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1

CLEAR INCIPENT FAULT COUNTERS
6 ACTUAL VALUES
SLOW EXCHANGE 1(2)

6.2.20 INCIPIENT FAULT DETECTOR