Samsung RVMC060GDM0 Technical Manual

Dv m air conditioner
Table of Contents

Advertisement

T M
S A M S U N G
D V M
Air Conditioner
SAMSUNG ELECTRONICS

Advertisement

Table of Contents
loading

Summary of Contents for Samsung RVMC060GDM0

  • Page 1 S A M S U N G D V M Air Conditioner SAMSUNG ELECTRONICS...
  • Page 2: Table Of Contents

    Ι ΙΙΙ Overview Indoor unit 1. DVM system series 1. Features 6. Refrigerant system diagram (Cooling only & heat pump) 1-1. What is DVM? 1-1. 1-way cassette type 1-2. Features of DVM 1-2. 4-way cassette type 6-1. Refrigerant system diagram 1-3.
  • Page 3 Ι Λ Λ Outdoor unit Installation 1. Unit selection 1. Product 8. Piping and refnet (with cooling load) joint selection 1-1. Preparation for installation 1-2. Deciding on where to install 8-1. Examples of using only the air conditioner 2. Specification Refnet joint 1-3.
  • Page 4 Ι Overview 1. DVM system series 1-1. What is DVM? 1-2. Features of DVM 2. DVM line-up 2-1. Numbering system of model 2-2. Combination...
  • Page 5: Dvm System Series

    Ι . Overview 1. DVM system series 1-1. What is DVM? The DVM(Digital Variable Multi) air conditioning system is operated by a variable-capacity compressor and is accommodated by multiple evaporators (indoor units). It is touted as the next-generation modular system in the world of high-efficiency air conditioning. lt has undoubtedly changed the face of cooling associated with high-storied buildings.
  • Page 6: Features Of Dvm

    1-2. Features of DVM (1) Customized air conditioner 1) Up to 16 indoor units can be connected to one outdoor unit. 2) Indoor units can be combined by various methods, according to each room’s use and shape. 3) There are several indoor units which can be applied; 1-way cassette type, 4-way cassette type, Ceiling, Duct (Low silhouette, Built-in, High pressure), Wall-mounted and Floor standing type.
  • Page 7 Ι . Overview 1. DVM system series (3) Variable compressor The world’s first PWM(Pulse Width Modulation) compressor controls the cooling & heating capacity automatically, depending on the load. 1) Principle of the digital compressor Composition The solenoid valve is installed for the compressor´s loading / unloading between the upper part of the fixed scroll and the suction pipe.
  • Page 8 2) PWM (Pulse Width Modulation) valve PWM valve is the valve to take away the fixed scroll by lifting up through the difference of pressure after the digital scroll compress being connected to the outlet and inlet of suction. Therefore, the capacity of compressor is controlled automatically according to the operation status such as loading when the valve is closed or unloading when the valve is opened.
  • Page 9 Comparison 100% 121% 148% The results are based on Samsung Lab., therefore there may be differences according to the condition of installation and the environment of the use. Heat loads : 90,000 kcal/h in Korea Total area : 750m Running : 3 months in every summer and winter...
  • Page 10 (9) Space Saving The outdoor units connected with several indoor units do not require much space. 1) Conventional System 2) DVM System...
  • Page 11: Dvm Line-Up

    Ι . Overview 2. DVM line-up 2-1. Numbering system of model (1) Indoor unit and outdoor unit (Conventional model) Model Semi-finished product Power supply - Indoor unit Indoor unit 115V, 60Hz Outdoor unit 220V, 60Hz 208~230V, 60Hz Classification of product 200~220V, 50Hz 1-way cassette type 220~240V, 50Hz...
  • Page 12 (2) Indoor unit and outdoor unit (New Model) 1) Indoor unit Model 0 0 0 Semi-finished product Mode Power supply Variable capacity free Cooling only (C/O) 208~230V, 60Hz joint multi (DVM) Heat pump (H/P) 220~240V, 50Hz H/P+Heater C/O+Heater C/O+Hot water heater Classification of product Capacity (x 1/10 kW, 3 digits) Refrigerant...
  • Page 13: Combination

    Ι . Overview 2. DVM line-up 2) Outdoor unit Model 0 0 0 Semi-finished product Power supply Combination of indoor unit Variable capacity free 208~230V, 60Hz 1-way joint multi (DVM) Cassette 208~230V, 60Hz, 3ø 4-way type 380~415V, 50Hz, 3ø 2-way 380V, 60Hz, 3ø...
  • Page 14: Wireless Remote Controller

    (3) Options Parts Model Standard for model name Example Electronic MEV : Optional electronic expansion valve MEV-14SA MEV- expansion : Electronic expansion valve model (2 digits) MEV-18SA valve kit : Manufacturer MEV-24SA (Attachment : Version type) Electronic MXD : Optional distributor kit MXD-14K300A MXD- expansion...
  • Page 15 Ι . Overview 2. DVM line-up Parts Model Standard for model name Example Receiver MRW : Optional receiver & display unit wire MRW-10A MRW- & display : Length (m, 2 digits) MRW-10AC unit wire : Version : Language (None: English, C: Chinese) Interface MIM : Optional interface module MIM-B00...
  • Page 16 Parts Model Standard for model name Example Duct MDP : Duct flange MDP-2030 MDP- flange : Hole size (ø, cm) MDP-2030C (For China) : Number of hole : Version Super MSC : Super cooler MSC-00EB0 MSC- cooler (Applied to the : HP of applicable outdoor unit top of 10.0HP (marked as 00 if it is 10.0 HP)
  • Page 17: Combination

    2. DVM line-up 2-2. Combination (1) Outdoor unit 1) Cooling only Design Power supply Model Capacity(HP) Refrigerant Main Super cooler 50Hz 380~415V, 3ø RVMC060GDM0 R407C 60Hz 208~230V, 1ø RVMC050CBM0 380~415V, 3ø RVMC060GAM0 50Hz 380~415V, 3ø RVMC060GAM1 380V, 3ø MUF7201F1 60Hz 208~230V, 3ø...
  • Page 18 Design Max. connectible Total capacity of indoor Super Remark indoor units units (kW, ISO standard) cooler Main Super cooler 8.0~20.8 7.2~18.8 8.0~20.8 8.0~16.0 For the Middle East 10.5~21.0 For the Middle East 10.5~27.3 10.5~21.0 For the Middle East 14.0~36.4 14.0~28.0 For the Middle East 14.0~36.4 14.0~28.0...
  • Page 19 Ι . Overview 2. DVM line-up 2) Heat pump Design Power supply Model Capacity(HP) Refrigerant Main Super cooler 380~415V, 3ø RVMH060GBM0 50Hz 380~415V, 3ø RVMH060GDM0 R407C 208~230V, 1ø RVMH050CBM0 60Hz 380~415V, 3ø RVMH080GAM0 380~415V, 3ø RVMH100GAM0 50Hz 380~415V, 3ø RVMH100GCM0 60Hz 208~230V, 3ø...
  • Page 20 Design Max. connectible Total capacity of indoor Super Remark indoor units units (kW, ISO standard) cooler Main Super cooler 8.0~20.8 8.0~20.8 7.2~18.8 11.0~29.0 14.0~36.4 14.0~28.0 For Middle East 14.0~36.4 14.0~36.4 14.0~28.0 For Middle East The system enables the connection of indoor units with a total capacity of between 50 to 130% of that of the corresponding outdoor unit but where this capacity ratio exceeds 100% then the actual capacity of each indoor unit will fall a little short of its individual rated capacity when all the units are operated simultaneously.
  • Page 21 Ι . Overview 2. DVM line-up (2) Indoor unit Power 2.0kW 2.6kW 3.2kW 3.5kW 4.0kW 5.2kW 6.0kW Design supply (7000Btu/h) (9000Btu/h) (11000Btu/h) (12000Btu/h) (13500Btu/h) (18000Btu/h) (20000Btu/h) 1-way cassette type AVMKC020EA0 AVMKC026EA0 AVMKC035EA0 50Hz AVMKH020EA0 AVMKH026EA0 AVMKH035EA0 AVMKC020CA0 AVMKC032CA0 AVMKC040CA0 60Hz AVMKH020CA0 AVMKH032CA0 AVMKH040CA0...
  • Page 22 Power 7.0kW 7.2kW 8.2kW 8.3kW 10.5kW 12.8kW Design Remark supply (24000Btu/h) (24000Btu/h) (28000Btu/h) (28000Btu/h) (36000Btu/h) (44000Btu/h) 1-way cassette type 50Hz 60Hz 4-way cassette type AVMCC070EA0 AVMCC105EA0 50Hz AVMCH070EA0 AVMCH105EA0 AVMCC072CA0 AVMCC105CA0 60Hz ABM2400B1 AVMCH105CA0 AVMCH072CA0 Duct type(Low silhouette) AVMDC070EA0 50Hz AVMDH070EA0 AVMDC072CA0 60Hz...
  • Page 23 ΙΙ Control system 1. Remote controller 1-1. Wireless remote controller 1-2. Wired remote controller 1-3. Centralized controller 1-4. Function controller 2. Receiver & display unit (Duct type) 2-1. Concealed type 2-2. Standard type 3. Interface module 4. Installation 4-1. Wireless remote controller 4-2.
  • Page 24: Remote Controller

    ΙΙ . Control System 1. Remote controller 1-1. Wireless remote controller (1) Cooling only Operating mode selection button Operating mode Temperature adjustment buttons Automatic Cool Filter Reset button Fan speed adjustment button Air flow direction adjustment button On timer button Off timer button On/Off &...
  • Page 25: Wired Remote Controller

    1-2. Wired remote controller (1) Cooling only Operating mode Automatic Cool Temperature On/Off & Timer set/cancel button adjustment buttons Operating indicator Fan speed adjustment button On/Off timer button Air flow direction adjustment button Test operation button Filter Reset button Operating mode selection button (2) Heat pump Operating mode...
  • Page 26: Centralized Controller

    ΙΙ . Control System 1. Remote controller 1-3. Centralized controller Operating lamp All On button All Off button On/off indicators Individual On/Off button Index 1-4. Function controller Operating mode On/Off button Temperature adjustment buttons Fan speed adjustment button Indoor unit selection buttons Air flow direction adjustment button Test button Filter reset button...
  • Page 27: Receiver & Display Unit (Duct Type)

    2. Receiver & display unit (For Duct) 2-1. Concealed type (1) Cooling only Filter sign indicator Fan indicator Timer indicator Remote control sensor On/Off button (2) Heat pump Filter sign indicator Fan indicator Timer indicator Remote control sensor On/Off button(Blue) & Removing frost indicator(Red) The shape of receiver &...
  • Page 28: Standard Type

    ΙΙ . Control System 2. Receiver & display unit (For Duct) 2-2. Standard type (1) Cooling only Filter sign indicator Remote control sensor On/Off indicator Fan indicator On/Off button Timer indicator (2) Heat pump Removing frost indicator Filter sign indicator Remote control sensor On/Off indicator Fan indicator...
  • Page 29: Interface Module

    3. Interface module Group address display CN01 Indoor unit address display To outdoor unit PCB (DC 12V) To centralized controller / S-Net converter F1 F2 Interface module address setting (Each Interface module has its own address) From F1, F2 terminal in the outdoor unit ΙΙ...
  • Page 30: Installation

    ΙΙ . Control System 4. Installation 4-1. Wireless remote controller (1) Accessories Wireless remote Battery for M4x12 tapped Remote control Owner’s Installation controller(1) wireless remote screw(2) holder(1) instructions(1) manual(1) controller(2) (2) Installation Choose a position where: The signal from the remote controller will not be blocked (by a curtain for example) The remote controller is not exposed to direct sunlight or heat The wireless remote controller is at least one meter away from...
  • Page 31: Wired Remote Controller

    4-2. Wired remote controller (1) Accessories Wired Remote Cable-Tie(2) Cable Clamp M4x16 Indoor Unit Owner’s Installation Controller (1) Tapped Screw Power Drawing instructions(1) manual (1) Cable (1) (2) Installation 1) Open the wired remote controller by using two grooves on its top.
  • Page 32 ΙΙ . Control System 4. Installation (3) Setting up option switches Indoor unit PCB 1) Adjust K1 DIP switch(SW03) on the PCB to the “OFF” K1 K2 K3 K4 position. SW03 2) Turn the arrow of RMC rotary switch(SW01) to the SW01 appropriate position.
  • Page 33 (4) Example of installing wired remote controller Individual control Means a wired remote controller controls only 1 indoor unit. In this case, the RMC address of the indoor unit should be the same with the address of wired remote controller. Indoor unit PCB K1 K2 K3 K4 Outdoor unit...
  • Page 34: Centralized Controller

    ΙΙ . Control System 4. Installation 4-3. Centralized controller (1) Accessories Centralized Cable-tie (2) Cable Clamp (5) M4x16 Tapped Owner’s Installation Controller (1) Screw (7) instructions(1) manual(1) If you would like to install the centralized controller, you must install the optional interface module in the outdoor unit.
  • Page 35 (4) Assigning address Turn the arrow of rotary switch on the interface module to appropriate position. Interface modules controlled with the same centralized controller must have different addresses. Interface module rotary switch (5) Setting up option switches In case of installing centralized controller only Adjust K2 DIP switch(SW03) on the indoor unit PCB to the K1 K2 K3 K4 “OFF”...
  • Page 36 ΙΙ . Control System 4. Installation In Case of Installing wired remote controller together 1) Adjust K2 DIP switch(SW03) on the indoor unit PCB to the K1 K2 K3 K4 “OFF” position. It means use of the centralized controller. SW03 The number of button on the centralized controller is decided by the RMC addresses of indoor units.
  • Page 37 (6) Example of centralized controller & wired remote controller Installation of 1 centralized controller, 4 outdoor units, and 12 indoor units 6 indoor units connected to the outdoor unit 1 and 2 are controlled with their own wired remote controller and a centralized controller. 3 indoor units connected to the outdoor unit 3 are controlled as a group by a wired remote controller and a centralized controller.
  • Page 38 ΙΙ . Control System 4. Installation Level of centralized controller Adjust the DIP switch on the centralized controller PCB, if necessary. Refer to the table below. Switch Meaning The air conditioner is operated by a con- troller adjusted the last among the wired and Level 0 OFF OFF OFF OFF wireless remote controller, and centralized controller.
  • Page 39 4-4. Function controller (1) Accessories Function Cable-tie(2) Cable clamp M4x16 Owner’s Installation controller (1) Tapped screw instructions(1) manual (1) (2) Installation 1) Disassemble the function controller by using a groove on its top. 2) Secure the rear cover of the function controller on the wall with two screws.
  • Page 40 ΙΙ . Control System 4. Installation (3) Wiring diagram Install the interface module, another optional accessory, in the outdoor unit which will be controlled by the centralized controller, then connect the function controller and the centralized controller to the interface module. Each outdoor unit connected to the same centralized controller must have its own interface module.
  • Page 41 4-5. Receiver & display unit - Concealed type (1) Accessories Receiver & STS 2S-2x10 2S-4x12 Tapped Owner’s Installation Wire kit Display Unit (1) Tapped Screw (4) Screw (2) instructions(1) manual(1) (Length:10m) (2) Installation 1) Remove the receiver & display unit cover by using the tab on its bottom.
  • Page 42 ΙΙ . Control System 4. Installation 4-6. Receiver & display unit - Standard type (1) Accessories Receiver & Cable-Tie(2) Cable Clamp M4x16 Owner’s Installation Wire kit display unit (1) Tapped Screw instructions(1) manual (1) (Length:10m) (2) Installation 1) Remove the receiver & display unit cover by using the tab on its bottom.
  • Page 43: Outdoor Unit

    4-7. Interface module (1) Accessories Interface module Interface module Interface module Installation power cable (1) communication manual (1) cable (1) CN01 F1 F2 (2) Installation Attach the interface module to the left side of the electrical component box in outdoor unit, then connect the power and communication cable between the interface module and the outdoor;...
  • Page 44: Module 1

    ΙΙ . Control System 4. Installation (3) Wiring diagram Each outdoor unit connected to the same centralized controller has its own interface module. Distance between the centralized controller and the last interface module should be 1000 meters or less. Outdoor unit 1 Indoor unit 1 Indoor unit 2 Indoor unit 3...
  • Page 45: Indoor Unit

    5. Assigning address 5-1. Indoor unit 1) Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan. 2) The address of the indoor unit is assigned by adjusting MAIN(SW02) and RMC(SW01) rotary switches.
  • Page 46 ΙΙ . Control System 5. Assigning address 5-2. Outdoor unit Rotary switch Outdoor unit PCB You should display that how many indoor units are connected to the outdoor unit. Refer to the table below, then turn the arrow to appropriate position. Number of indoor Number of indoor Switch No.
  • Page 47 6. Indoor unit PCB option code 6-1. PCB option code input method (example : 021E31142285) Be sure to input the option code suitable for the indoor unit by use of wireless remote controller after replacing the PCB of indoor unit. Follow to do the following 15 steps sequentially.
  • Page 48 ΙΙ . Control System 6. Indoor unit PCB option code Operation method Applicable button Indicating state Step 4 Method) Input the third digit of option code by pressing the temperature adjustment button (down). example) 021E31142285 Result) If 1 is displayed, go to the step 5. Step 5 Method) Input the fourth digit of option...
  • Page 49 Operation method Applicable button Indicating state Step 7 Method) Input the sixth digit by pressing the Off timer button. example) 021E31142285 Result) If 1 displays, go to step 8. Step 8 Method) After completion up to step 7, pressing mode button. 1 ~ 7 steps are saved internally.
  • Page 50 ΙΙ . Control System 6. Indoor unit PCB option code Operation method Applicable button Indicating state Step 10 Method) Input the ninth digit by pressing the temperature adjustment button (down). example) 021E31142285 Result) If 2 displays, go to step 11. Step 11 Method) Input the tenth digit by pressing...
  • Page 51 Operation method Applicable button Indicating state Step 13 Method) Input the 12th digit by pressing the Off timer button. example) 021E31142285 Result) If 5 displays, go to step 14. Step 14 Error If the On/Off, Timer and Fan Method) indicator is flickering, the wrong Turn the remote controller toward option code is input.
  • Page 52 ΙΙ . Control System 6. Indoor unit PCB option code 6-2. Option code Type Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Remark AVMKC020EA0 AVMKC020CA0 AVMKC026EA0 AVMKC032CA0 AVMKC035EA0 1-way AVMKC040CA0 Cassette AVMKH020EA0 type AVMKH020CA0 AVMKH026EA0 AVMKH032CA0 AVMKH035EA0 AVMKH040CA0...
  • Page 53 Type Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Remark AVMBC020EA0 AVMBC020CA0 AVMBC026EA0 AVMBC032CA0 AVMBC035EA0 AVMBC040CA0 AVMBC052EA0 AVMBC052CA0 AVMBC070EA0 Duct AVMBC072CA0 type AVMBH020EA0 (Built-in) AVMBH020CA0 AVMBH026EA0 AVMBH032CA0 AVMBH035EA0 AVMBH040CA0 AVMBH052EA0 AVMBH052CA0 AVMBH070EA0 AVMBH072CA0 AVMHC105EA0 AVMHC105CA0 AVMHC128EA0 Duct AVMHC128CA0...
  • Page 54 ΙΙ . Control System 6. Indoor unit PCB option code 6-2. Option code Type Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Remark AVMWC020EA0 AVMWC020CA0 AVMWC026EA0 AVMWC032CA0 AVMWC035EA0 AVMWC040CA0 AVMWC052EA0 AVMWC052CA0 AVMWC070EA0 Wall- AVMWC072CA0 mounted AVMWH020EA0 type AVMWH020CA0...
  • Page 55 7. S-Net Interface module PCB Rear of computer (Not supplied) Switch of converter slide Oudoor unit PCB Power Power Connector COM1 port 1) Download S-NET program to your PC, then execute Setup.exe to install the program. 2) If the installation is completed successfully, connect RS-485 converter to COM1 or COM2 port on your computer.
  • Page 56 ΙΙ . Control System 8. Integrating power distribution system ΙΙ...
  • Page 57 9. Building management system ΙΙ...
  • Page 58 ΙΙΙ Indoor unit 1. Features 6. Refrigerant system diagram (Cooling only & heat pump) 1-1. 1-way cassette type 1-2. 4-way cassette type 6-1. Refrigerant system diagram 1-3. Duct type 6-2. Main parts status 1-4. Wall-mounted type 1-5. Floor standing type 7.
  • Page 59: Way Cassette Type

    ΙΙΙ . Indoor unit 1. Features 1-1. 1-Way cassette type (1) Efficient cooling & stylish design This type sends cool air from the ceiling to one direction; thus immediate cooling. Even more, the stylish design blends with any interior design. (2) Space saving Installation in the ceiling translates to more available space in the room.
  • Page 60: Wired Remote Controller

    The long-life filter requires no maintenance for up to 2,000 hours. 2) Bio heat exchanger & air filter Samsung’s own heat exchanger and air filter prevent any penetration of fungi or bacteria into the system. Insulating material (Foam PU) 3) Double-insulated cabinet...
  • Page 61: Way Cassette Type

    ΙΙΙ . Indoor unit 1. Features 1-2. 4-Way cassette type (1) Powerful functions The 4-way cassette type air conditioner has all the features of the 1-way cassette type; compact design, long-life air filter, bio heat exchanger, lift-up drain pump, etc. (2) Higher &...
  • Page 62 (3) Features of 4-way cassette type 1) Fan speed adjustment Item Ceiling height Fan speed can be adjusted 2.7~3.5m 3.5m according to the ceiling height. 2.7m Max. installation ceiling height is 3.5 meters. 2) Versatile airflow The direction of airflow can be selected to meet installation or room specifications.
  • Page 63: Duct Type

    ΙΙΙ . Indoor unit 1. Features 1-3. Duct type (1) Economic installation Several diffusers branch off from an indoor unit, adjusting the room temperature, which makes many rooms to be air conditioned with only one indoor unit. Looks of installed Duct (Built-in type) (2) High external static pressure Adjustable external static pressure allows ducts from the unit to be used more extensively.
  • Page 64: Duct Type

    (3) Features of Duct type 1) Application methods L-shaped area Y-shaped area Areas far apart 2) Way of air intake & Inserting air filter Air intake can be positioned either at the back or below the unit. Similarly, the air filter can be inserted either from the back or from the bottom of the unit.
  • Page 65: Wall-Mounted Type

    1-4. Wall-mounted type (1) BIO-components Samsung air conditioners ensure cleaner cooling than any other air conditioner. The components of our air conditioners (including the filters) have been treated with our unique antibacterial formula, which prevent the proliferation of fungi and bacteria within the unit, helping to keep the unit clean, and to block odors from developing.
  • Page 66 Our new air conditioners are extremely compact Conventional and much lighter than previous models, making them extremely easy to handle and install. Additionally, with its stylish design, a Samsung air conditioner will be an attractive addition to any home or office. Volume 28% Down 4) Easily detachable and washable front grille It is easy to clean as the grille can be pulled apart and easy to replace as it just slides in.
  • Page 67: Floor Standing Type

    ΙΙΙ . Indoor unit 1. Features 1-5. Floor standing type (1) Features of floor standing type 1) The auto shutter increased cleanliness The auto shutter protects the air conditioner from dust even without a cover and the air conditioner goes well with any home. ‘On’...
  • Page 68 5) Design Air flow blades (right/left orientation) Air flow blades (up/down orientation) Air outlet Automatic shutter Air filter Air inlet Control panel Removing frost indicator On/Off indicator Fan indicator Timer indicator Filter indicator ΙΙΙ...
  • Page 69: Ceiling Type

    ΙΙΙ . Indoor unit 1. Features 1-6. Ceiling type (1) Convenient installation The ceiling type air conditioner can be easily installed into a corner of the ceiling even if the ceiling is very narrow. This is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as a lighting fixture.
  • Page 70: Installation

    (3) Features of ceiling type 1) Long life filter with antibacterial treatment The detachable filter can be cleaned easily, thus controlling the propagation of fungi & bacteria. 2) Drain water lift-up mechanism (Optional) The “Drain water lift-up” mechanism offers more flexible installation.
  • Page 71: Specification

    ΙΙΙ . Indoor unit 2. Specification 2-1. 1-way cassette type (1) 50Hz Model AVMKC020EA0 AVMKC026EA0 AVMKC035EA0 AVMKH020EA0 AVMKH026EA0 AVMKH035EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 7000 9000 12000 7000 9000...
  • Page 72: Centralized Controller

    (2) 60Hz Model AVMKC020CA0 AVMKC032CA0 AVMKC040CA0 AVMKH020CA0 AVMKH032CA0 AVMKH040CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 7000 11000 13500 7000 11000 13500 Heating Btu/h 7500 12000 14500 Sound Level Cooling (High/Low) 32/29 36/32...
  • Page 73: 4-Way Cassette Type

    ΙΙΙ . Indoor unit 2. Specification 2-2. 4-way cassette type (1) 50Hz Model AVMCC052EA0 AVMCC070EA0 AVMCC105EA0 AVMCH052EA0 AVMCH070EA0 AVMCH105EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 18000 24000 36000 18000 24000...
  • Page 74 (2) 60Hz Model AVMCC052CA0 AVMCC072CA0 AVMCC105CA0 AVMCH052CA0 AVMCH072CA0 AVMCH105CA0 ABM1800B1 ABM2400B1 ø, V, Hz 1, 208 ~ 230, 60 Power supply Remark Cooling only Heat pump Capacity Cooling Btu/h 18000 24000 36000 18000 24000 36000 Performance 10.5 10.5 Heating Btu/h 19000 26000 39000...
  • Page 75: Duct Type (Low Silhouette)

    ΙΙΙ . Indoor unit 2. Specification 2-3. Duct type (Low silhouette) (1) 50Hz Model AVMDC052EA0 AVMDC070EA0 AVMDH052EA0 AVMDH070EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 18000 24000 18000 24000 Heating Btu/h...
  • Page 76 (2) 60Hz AVMDC052CA0 AVMDC072CA0 AVMDH052CA0 AVMDH072CA0 Model ADM1800B1 ADM2400B1 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 18000 24000 18000 24000 Heating Btu/h 19000 26000 Sound Level Cooling (High/Low) 34/32 38/36 34/32...
  • Page 77: Duct Type (Built-In)

    ΙΙΙ . Indoor unit 2. Specification 2-4. Duct type (Built-in) (1) 50Hz Model AVMBC020EA0 AVMBC026EA0 AVMBC035EA0 AVMBC052EA0 AVMBC070EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Performance Capacity Cooling Btu/h 7000 9000 12000 18000 24000 Heating Btu/h Sound Level...
  • Page 78 Model AVMBH020EA0 AVMBH026EA0 AVMBH035EA0 AVMBH052EA0 AVMBH070EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Heat pump Performance Capacity Cooling Btu/h 7000 9000 12000 18000 24000 Heating Btu/h 7500 10000 13000 19000 26000 Sound Level Cooling (High/Low) 37/34 41/38 42/39 43/40...
  • Page 79 ΙΙΙ . Indoor unit 2. Specification (2) 60Hz Model AVMBC020CA0 AVMBC032CA0 AVMBC040CA0 AVMBC052CA0 AVMBC072CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Performance Capacity Cooling Btu/h 7000 11000 13500 18000 24000 Heating Btu/h Sound Level Cooling (High/Low) 37/34 41/38...
  • Page 80 Model AVMBH020CA0 AVMBH032CA0 AVMBH040CA0 AVMBH052CA0 AVMBH072CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Heat pump Performance Capacity Cooling Btu/h 7000 11000 13500 18000 24000 Heating Btu/h 7500 12000 14500 19000 26000 Sound Level Cooling (High/Low) 37/34 41/38 42/39 43/40...
  • Page 81: Duct Type (High Pressure)

    ΙΙΙ . Indoor unit 2. Specification 2-5. Duct type (High pressure) (1) 50Hz Model AVMHC105EA0 AVMHC128EA0 AVMHH105EA0 AVMHH128EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 36000 44000 36000 44000 10.5 12.8...
  • Page 82 (2) 60Hz Model AVMHC105CA0 AVMHC128CA0 AVMHH105CA0 AVMHH128CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 36000 44000 36000 44000 10.5 12.8 10.5 12.8 Heating Btu/h 39000 47000 11.4 13.8 Sound Level Cooling (High/Low) 45/44...
  • Page 83: Wall-Mounted Type

    ΙΙΙ . Indoor unit 2. Specification 2-6. Wall-mounted type (1) 50Hz Model AVMWC020EA0 AVMWC026EA0 AVMWC035EA0 AVMWC052EA0 AVMWC070EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Performance Capacity Cooling Btu/h 7000 9000 12000 18000 24000 Heating Btu/h Sound Level Cooling (High/Low)
  • Page 84 Model AVMWH020EA0 AVMWH026EA0 AVMWH035EA0 AVMWH052EA0 AVMWH070EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Heat pump Performance Capacity Cooling Btu/h 7000 9000 12000 18000 24000 Heating Btu/h 7500 11000 13000 19000 26000 Sound Level Cooling (High/Low) 29/28 34/30 38/35 43/39...
  • Page 85 ΙΙΙ . Indoor unit 2. Specification (2) 60Hz Model AVMWC020CA0 AVMWC032CA0 AVMWC040CA0 AVMWC052CA0 AVMWC072CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Performance Capacity Cooling Btu/h 7000 11000 13500 18000 24000 Heating Btu/h Sound Level Cooling (High/Low) 29/28 34/30...
  • Page 86 Model AVMWH020CA0 AVMWH032CA0 AVMWH040CA0 AVMWH052CA0 AVMWH072CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Heat pump Performance Capacity Cooling Btu/h 7000 11000 13500 18000 24000 Heating Btu/h 7500 12000 14500 19000 26000 Sound Level Cooling (High/Low) 29/28 34/30 38/35 43/39...
  • Page 87: Floor Standing Type

    ΙΙΙ . Indoor unit 2. Specification 2-7. Floor standing type (1) 50Hz Model AVMPC060EA0 AVMPC070EA0 AVMPC082EA0 AVMPH060EA0 AVMPH070EA0 AVMPH082EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 20000 24000 28000 20000 24000...
  • Page 88 (2) 60Hz Model AVMPC060CA0 AVMPC072CA0 AVMPC083CA0 AVMPH060CA0 AVMPH072CA0 AVMPH083CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 20000 24000 28000 20000 24000 28000 Heating Btu/h 22000 26000 30000 Sound Level Cooling (High/Low) 37/35 42/40...
  • Page 89: Ceiling Type

    ΙΙΙ . Indoor unit 2. Specification 2-8. Ceiling type (1) 50Hz Model AVMFC052EA0 AVMFC070EA0 AVMFH052EA0 AVMFH070EA0 Power supply ø, V, Hz 1, 220 ~ 240, 50 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 18000 24000 18000 24000 Heating Btu/h 19000 26000...
  • Page 90: Cooling Only

    (2) 60Hz Model AVMFC052CA0 AVMFC072CA0 AVMFH052CA0 AVMFH072CA0 Power supply ø, V, Hz 1, 208 ~ 230, 60 Remark Cooling only Heat pump Performance Capacity Cooling Btu/h 18000 24000 18000 24000 Heating Btu/h 19000 26000 Sound Level Cooling (High/Low) 43/40 45/40 43/40 45/40 Heating (High/Low)
  • Page 91: Functional Parts And Safety Devices

    ΙΙΙ . Indoor unit 3. Functional parts and safety devices 3-1. 1-way cassette type AVMKC020EA0 AVMKC026EA0 AVMKC032CA0 AVMKC035EA0 AVMKC040CA0 AVMKH020EA0 AVMKH026EA0 AVMKH032CA0 AVMKH035EA0 AVMKH040CA0 Item Code Name AVMKC020CA0 AVMKH020CA0 PFS040WTVE PFS040WTVE PFS040WTVE PFS040WTVE model PFS040WTVEW Fan motor output Safety Motor 168°C 168°C 168°C...
  • Page 92: Duct Type (Low Silhouette)

    3-3. Duct type (Low silhouette) ADM1800B1 ADM2400B1 AVMDC052EA0 AVMDC052CA0 AVMDC070EA0 Item Code Name AVMDH052EA0 AVMDH052CA0 AVMDH070EA0 OSM956SAC OSM1304SAC OSME1004SAC OSM956SAC OSME1004SAC model Fan motor Safety output Motor devices 135°C 135°C 135°C 135°C 135°C Safety thermostat 90°C 90°C 90°C 90°C 90°C Thermistor (heat exchanger inlet) 103AT (25°C=10kΩ) Temperature...
  • Page 93: Duct Type (Built-In)

    ΙΙΙ . Indoor unit 3. Functional parts and safety devices 3-4. Duct type (Built-in) AVMBC020EA0 AVMBC020CA0 AVMBC026EA0 AVMBC032CA0 AVMBC035EA0 Item Code Name AVMBH020EA0 AVMBH020CA0 AVMBH026EA0 AVMBH032CA0 AVMBH035EA0 OSME414SAC OSM404SAC OSME414SAC OSM404SAC OSME414SAC model Fan motor Safety output Motor devices 135°C 135°C 135°C 135°C...
  • Page 94: Wall-Mounted Type

    3-6. Wall-mounted type AVMWC020EA0 AVMWC026EA0 AVMWC032CA0 AVMWC035EA0 AVMWC040CA0 AVMWH020EA0 AVMWH026EA0 AVMWH032CA0 AVMWH035EA0 AVMWH040CA0 Item Code Name AVMWC020CA0 AVMWH020CA0 YFNPG22-4 YFNPG22-4 YFNPG22-4 YFNPG22-4 YFNPG22-4 model Fan motor Safety output Motor devices 163°C 163°C 163°C 163°C 163°C Safety thermostat Thermistor (heat exchanger inlet) 103AT (25°C=10kΩ) Temperature Thermistor (heat exchanger outlet)
  • Page 95: Floor Standing Type

    ΙΙΙ . Indoor unit 3. Functional parts and safety devices 3-7. Floor standing type AVMPC060EA0 AVMPC060CA0 AVMPC070EA0 AVMPC072CA0 AVMPC082EA0 Item Code Name AVMPH060EA0 AVMPH060CA0 AVMPH070EA0 AVMPH072CA0 AVMPH082EA0 OSM1408SAC OSM1308SAC OSM1408SAC OSM1308SAC OSM1408SAC model Fan motor output Safety Motor 135°C 135°C 135°C 135°C 135°C...
  • Page 96 4. Capacity table 4-1. 50Hz (1) Cooling TC : Total capacity Indoor temperature (ºC, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Unit Size temperature (ºC, DB) 1.46 1.73 2.05 2.16 2.30 2.56 2.83 1.46 1.73 2.05 2.16 2.30 2.56 2.83 1.46...
  • Page 97 ΙΙΙ . Indoor unit 4. Capacity table TC : Total capacity Indoor temperature (ºC, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Unit Size temperature (ºC, DB) 3.81 4.49 5.34 5.63 5.98 6.67 7.37 3.81 4.49 5.34 5.63 5.98 6.67 7.37 3.81...
  • Page 98 TC : Total capacity Indoor temperature (ºC, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Unit Size temperature (ºC, DB) 7.68 9.07 10.79 11.36 12.07 13.46 14.88 7.68 9.07 10.79 11.36 12.07 13.46 14.88 7.68 9.07 10.79 11.36 12.07 13.46 14.88 7.68...
  • Page 99 ΙΙΙ . Indoor unit 4. Capacity table (2) Heating TC : Total capacity Indoor temperature (ºC, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (ºC) Unit Size 1.45 1.43 1.40 1.39 1.36 1.63 1.61 1.59 1.56 1.54 1.83 1.78 1.74 1.72 1.69 1.98...
  • Page 100 TC : Total capacity Indoor temperature (ºC, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (ºC) Unit Size 10.3 10.0 11.1 10.6 10.2 10.0 11.6 11.2 10.8 10.5 12.1 11.6 11.4 10.5 12.3 12.1 11.4 10.5 12.8 12.3 11.4 10.5 13.1 12.3 11.4...
  • Page 101 ΙΙΙ . Indoor unit 4. Capacity table TC : Total capacity Indoor temperature (ºC, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (ºC) Unit Size 10.2 10.1 10.0 11.5 11.2 10.9 10.8 10.6 12.4 12.1 11.8 11.5 11.2 13.4 12.8 12.4 12.1 11.9...
  • Page 102 4-2. 60Hz (1) Cooling TC : Total capacity Indoor temperature (ºC, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Unit Size temperature (ºC, WB) 1.46 1.73 2.05 2.16 2.30 2.56 2.83 1.46 1.73 2.05 2.16 2.30 2.56 2.83 1.46 1.73 2.05 2.16...
  • Page 103 ΙΙΙ . Indoor unit 4. Capacity table TC : Total capacity Indoor temperature (ºC, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Unit Size temperature (ºC, WB) 3.81 4.49 5.34 5.63 5.98 6.67 7.37 3.81 4.49 5.34 5.63 5.98 6.67 7.37 3.81...
  • Page 104 TC : Total capacity Indoor temperature (ºC, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Unit Size temperature (ºC, WB) 10.8 11.4 12.1 13.5 14.9 10.8 11.4 12.1 13.5 14.9 10.8 11.4 12.1 13.5 14.9 10.8 11.4 12.1 13.5 14.9 10.8 11.4...
  • Page 105 ΙΙΙ . Indoor unit 4. Capacity table (2) Heating TC : Total capacity Indoor temperature (ºC, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (ºC) Unit Size 1.45 1.43 1.40 1.39 1.36 1.63 1.61 1.59 1.56 1.54 1.83 1.78 1.74 1.72 1.69 1.98...
  • Page 106 TC : Total capacity Indoor temperature (ºC, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (ºC) Unit Size 10.3 10.0 11.1 10.6 10.2 10.0 11.6 11.2 10.8 10.5 12.1 11.6 11.4 10.5 12.3 12.1 11.4 10.5 12.8 12.3 11.4 10.5 13.1 12.3 11.4...
  • Page 107 ΙΙΙ . Indoor unit 4. Capacity table TC : Total capacity Indoor temperature (ºC, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (ºC) Unit Size 10.2 10.1 10.0 11.5 11.2 10.9 10.8 10.6 12.4 12.1 11.8 11.5 11.2 13.4 12.8 12.4 12.1 11.9...
  • Page 108: Way Cassette Type

    5. Dimension 5-1. 1-way cassette type Unit : mm Check the position of remote control sensor and indicators before installing the unit. If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 109: Way Cassette Type

    ΙΙΙ . Indoor unit 5. Dimension 5-2. 4-way cassette type (1) 5.2kW ~ 7.2kW Unit : mm Check the position of remote control sensor and indicators before installing the unit. If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 110 (2) 10.5kW Unit : mm Check the position of remote control sensor and indicators before installing the unit. If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 111: Duct Type (Low Silhouette)

    ΙΙΙ . Indoor unit 5. Dimension 5-3. Duct type (Low silhouette) Unit : mm If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 112: Duct Type (Built-In)

    5-4. Duct type (Built-in) (1) 2.0kW ~ 4.0kW Unit : mm If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 113 ΙΙΙ . Indoor unit 5. Dimension (2) 5.2kW ~ 7.2kW Unit : mm If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 114: Duct Type (High Pressure)

    5-5. Duct type (High pressure) Unit : mm If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 115: Wall-Mounted Type

    ΙΙΙ . Indoor unit 5. Dimension 5-6. Wall-mounted type (1) 2.0kW ~ 4.0kW Unit : mm pipe hole ( 65) If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 116 (2) 5.2kW ~ 7.2kW Unit : mm pipe hole ( 65) If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 117: Floor Standing Type

    ΙΙΙ . Indoor unit 5. Dimension 5-7. Floor standing type Unit : mm If you want to install optional parts, refer to an appropriate installation manual. ΙΙΙ...
  • Page 118: Ceiling Type

    5-8. Ceiling type Unit : mm ΙΙΙ...
  • Page 119: Wireless Remote Controller Receiver & Display Unit

    ΙΙΙ . Indoor unit 5. Dimension 5-9. Wireless remote controller / Receiver & display unit (1) Wireless remote controller ΙΙΙ...
  • Page 120: Heat Pump

    (2) Display unit 1) 1-Way cassette type Cooling only Remote control sensor Timer indicator Fan indicator On/off indicator Filter sign indicator Heat pump Remote control sensor Timer indicator Fan indicator On/off(Green) & Removing Filter sign indicator frost(Red) indicator Both cooling only models and heat pump models use the same panel. However, the function of LED is different with each other.
  • Page 121 ΙΙΙ . Indoor unit 5. Dimension 2) 4-Way cassette type Cooling only Timer indicator On/off button Remote control sensor Fan indicator On/off indicator Removing frost indicator Filter sign indicator (Not operated) Heat pump Timer indicator On/off button Remote control sensor Fan indicator On/off indicator Removing frost...
  • Page 122 3) Wall-mounted type 2.0kW ~ 4.0kW - Cooling only Timer indicator Remote control sensor On/off indicator Filter sign indicator On/off button Fan indicator - Heat pump Timer indicator Remote control sensor On/off(Green) & Removing Filter sign indicator frost(Red) indicator On/off button Fan indicator ΙΙΙ...
  • Page 123 ΙΙΙ . Indoor unit 5. Dimension 5.2kW ~ 7.2kW - Cooling only On/Off indicator Filter sign indicator Fan indicator Timer indicator - Heat pump Removing frost indicator On/Off indicator Filter sign indicator Fan indicator Timer indicator ΙΙΙ...
  • Page 124 4) Floor standing type Cooling only On/Off indicator Fan indicator Timer indicator Filter sign indicator Heat pump Removing Fan indicator On/Off indicator frost indicator Timer indicator Filter sign indicator ΙΙΙ...
  • Page 125 ΙΙΙ . Indoor unit 5. Dimension 5) Ceiling type Cooling only Heat pump ΙΙΙ...
  • Page 126 (3) Receiver 1) Concealed type Unit : mm 2) Standard type ΙΙΙ...
  • Page 127: Wired Remote Controller

    ΙΙΙ . Indoor unit 5. Dimension 5-10. Wired remote controller Unit : mm ΙΙΙ...
  • Page 128: Centralized Controller

    5-11. Centralized controller Unit : mm 5-12. Function controller Unit : mm ΙΙΙ...
  • Page 129: Electronic Expansion Valve Kit (Distributor Kit Type)

    ΙΙΙ . Indoor unit 5. Dimension 5-13. Electronic expansion valve kit (Distributor kit type) Unit : mm ΙΙΙ...
  • Page 130: Refrigerant System Diagram

    6. Refrigerant system diagram (Cooling only & heat pump) 6-1. Refrigerant system diagram electronic expansion valve kit temperature sensor motor strainer strainer heat exchanger temperature sensor temperature sensor 6-2. Main parts status (1) Temperature sensor (EIS, Evaporator Inlet Sensor) The means to measure the refrigerant temperature at the inlet of heat exchanger which is used as the data for control of electronic expansion valve.
  • Page 131: Way Cassette Type

    ΙΙΙ . Indoor unit 7. Electric circuit diagram 7-1. 1-way cassette type (1) Cooling only (AVMKC ) ΙΙΙ...
  • Page 132 (2) Heat pump (AVMKH ) ΙΙΙ...
  • Page 133: Way Cassette Type

    ΙΙΙ . Indoor unit 7. Electric circuit diagram 7-2. 4-way cassette type (1) Cooling only (AVMCC ) ΙΙΙ...
  • Page 134 (2) Heat pump (AVMCH ) ΙΙΙ...
  • Page 135: Duct Type

    ΙΙΙ . Indoor unit 7. Electric circuit diagram 7-3. Duct type (1) Cooling only (AVMDC / AVMBC / AVMHC ) ΙΙΙ...
  • Page 136 (2) Heat pump (AVMDH / AVMBH / AVMHH ) ΙΙΙ...
  • Page 137: Wall-Mounted Type

    ΙΙΙ . Indoor unit 7. Electric circuit diagram 7-4. Wall-mounted type (1) Cooling only (AVMWC ) ΙΙΙ...
  • Page 138 (2) Heat pump (AVMWH ) ΙΙΙ...
  • Page 139: Floor Standing Type

    ΙΙΙ . Indoor unit 7. Electric circuit diagram 7-5. Floor standing type (1) Cooling only (AVMPC ) ΙΙΙ...
  • Page 140 (2) Heat pump (AVMPH ) ΙΙΙ...
  • Page 141: Ceiling Type

    ΙΙΙ . Indoor unit 7. Electric circuit diagram 7-6. Ceiling type (1) Cooling only (AVMFC ) ΙΙΙ...
  • Page 142 (2) Heat pump (AVMFH ) ΙΙΙ...
  • Page 143: Overall

    ΙΙΙ . Indoor unit 8. Noise level 8-1. Overall 1-way cassette type 4-way cassette type Duct type(Low silhouette) Duct Duct 1.5m 1.5m Microphone Microphone Microphone 230V/50Hz 220V/60Hz 230V/50Hz 220V/60Hz 230V/50Hz 220V/60Hz Model Model Model High High High High High High 32.0 29.0 32.0...
  • Page 144: Octave Band Level

    8-2. Octave band level (1) 1-way cassette type 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 026/032 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50...
  • Page 145 ΙΙΙ . Indoor unit 8. Noise level 035/040 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) ΙΙΙ...
  • Page 146 (2) 4-way cassette type 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 070/072 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0...
  • Page 147 ΙΙΙ . Indoor unit 8. Noise level 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) ΙΙΙ...
  • Page 148 (3) Duct type (Low silhouette) 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 070/072 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40...
  • Page 149 ΙΙΙ . Indoor unit 8. Noise level (4) Duct type (Built-in) 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 026/032 70.0 NC-65 60.0 NC-60...
  • Page 150 035/040 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25...
  • Page 151 ΙΙΙ . Indoor unit 8. Noise level 070/072 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) ΙΙΙ...
  • Page 152 (5) Duct type (High pressure) 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0...
  • Page 153 ΙΙΙ . Indoor unit 8. Noise level (6) Wall-mounted type 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 026/032 70.0 NC-65 60.0 NC-60 50.0...
  • Page 154 035/040 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25...
  • Page 155 ΙΙΙ . Indoor unit 8. Noise level 070/072 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) ΙΙΙ...
  • Page 156 (7) Floor standing type 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 070/072 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0...
  • Page 157 ΙΙΙ . Indoor unit 8. Noise level 082/083 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) ΙΙΙ...
  • Page 158 (8) Ceiling type 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High 10.0 NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 070/072 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35...
  • Page 159: Way Cassette Type

    ΙΙΙ . Indoor unit 9. Velocity of air flow & temperature distribution 9-1. 1-way cassette type (1) AVMKH035 1) Velocity of air flow 2.0m/sec 1.5m/sec 1.0m/sec 2) Heating temperature distribution If a ceiling is high, you can apply a 1-way cassette type air conditioner. The standard ceiling height is 3 meters and those values are tested at the standard height.
  • Page 160: Way Cassette Type

    9-2. 4-way cassette type (1) AVMCH070 1) Velocity of air flow m/sec m/sec m/sec 2) Heating temperature distribution The standard ceiling height is 2.7 meters and those values are tested at the standard height. ΙΙΙ...
  • Page 161 ΙΙΙ . Indoor unit 9. Velocity of air flow & temperature distribution (2) AVMCH105 1) Velocity of air flow m/sec m/sec m/sec m/sec 2) Heating temperature distribution The standard ceiling height is 2.7 meters and those values are tested at the standard height. ΙΙΙ...
  • Page 162: Wall-Mounted Type

    9-3. Wall-mounted type (1) AVMWH035 1) Velocity of air flow m/sec m/sec m/sec 2) Heating temperature distribution The standard ceiling height is 2.7 meters and those values are tested at the standard height. ΙΙΙ...
  • Page 163 ΙΙΙ . Indoor unit 9. Velocity of air flow & temperature distribution (2) AVMWH070 1) Velocity of air flow m/sec m/sec m/sec m/sec 2) Heating temperature distribution The standard ceiling height is 2.7 meters and those values are tested at the standard height. ΙΙΙ...
  • Page 164: Ceiling Type

    9-4. Ceiling type (1) AVMFH070 1) Velocity of air flow m/sec m/sec m/sec 2) Heating temperature distribution The standard ceiling height is 2.7 meters and those values are tested at the standard height. ΙΙΙ...
  • Page 165: Duct Type(Low Silhouette)

    ΙΙΙ . Indoor unit 10. Fan specifications 10-1. Duct type (Low silhouette) 070/072 Reliable Reliable TURBO TURBO Range of Range of normal use normal use Reliable Reliable Fan Speed (CMM) Fan Speed (CMM) 10-2. Duct type (Built-in) 026/032 TURBO Limitation of use Limitation of use TURBO Fan speed (m...
  • Page 166 035/040 TURBO Limitation of use TURBO Limitation of use 9 10 11 12 13 14 15 16 17 18 19 20 Fan speed (m /min) Fan speed (m /min) 070/072 Limitation of use TURBO 13 14 15 16 17 18 19 20 21 22 23 24 Fan speed (m /min) ΙΙΙ...
  • Page 167: Duct Type(High Pressure)

    ΙΙΙ . Indoor unit 10. Fan specifications 10-3. Duct type (High pressure) TURBO TURBO Air flow (m /min) Air flow (m /min) ΙΙΙ...
  • Page 168: Way Cassette Type

    11. Panel 11-1. 1-way cassette type (1) Design (2) Status Item Model Language (Manual) MGKH118IE0 English only Cooling only MGKH118IM0 English, Spanish, Italian, Portuguese, French, German, Greek, Russian & MGKH118IA0 English, Arabic, Spanish, French MGKH118IC0 Chinese, English Heat pump MGKH118IU0 English, Spanish, French ( F &...
  • Page 169: Way Cassette Type

    ΙΙΙ . Indoor unit 11. Panel 11-2. 4-way cassette type (1) Design (2) Status Item Model Language (Manual) MGCH095IE0 English only Cooling only MGCH095IM0 English, Spanish, Italian, Portuguese, French, German, Greek, Russian & MGCH095IA0 English, Arabic, Spanish, French MGCH095IC0 Heat pump Chinese, English MGCH095IU0 English, Spanish, French (...
  • Page 170: Built-In Type

    12. Electronic expansion valve kit 12-1. Built-in type Model Capacity Remark MEV-14SA 2.0kW ~ 4.0kW MEV-18SA 5.2kW ~ 8.3kW MEV-24SA 10.5kW MEV-14SB 2.0kW ~ 4.0kW MEV-18SB 5.2kW ~ 8.3kW for China MEV-24SB 10.5kW 12-2. Distributor kit type 14SA 18SA Item Remark MXD-14K300A MXD-14K218A...
  • Page 171 ΙΙΙ . Indoor unit 13. Options Mandatory items Electronic expansion valve kit Panel Item Remote Built-in Distributor controller type kit type 1-way cassette type Integrated 4-way cassette type Integrated Integrated Low silhouette Integrated Integrated Duct Built-in type Integrated Integrated High pressure Integrated Wall-mounted type Floor standing type...
  • Page 172 Optional items Drain pump Wireless Receiver & Receiver & Receiver & Wired remote Fresh air display unit Item display unit remote display controller intake (Standard (Concealed controller unit type) type) wire Integrated MR-AC01 MWR-AH01 1-way cassette type Integrated MR-AH01 MWR-AH01 Integrated MR-AC01 MWR-AH01...
  • Page 173 Outdoor unit 1. Selection of outdoor units (based on cooling load) 2. Specification 2-1. 50Hz 2-2. 60Hz 3. Functional parts and safety devices 4. Capacity table 4-1. 50Hz 4-2. 60Hz 5. Dimension 5-1. Upward (2-FAN) 5-2. Onward 5-3. Upward (1-FAN) 5-4.
  • Page 174: Outdoor Unit Selection

    Ι Λ . Outdoor unit 1. Unit selection (with cooling load) 1-1. Indoor unit selection Select the nearest load capacity indoor unit with given load after finding indoor and outdoor temperature using indoor unit capacity table. (The indoor unit capacity should larger than given load.) The described capacity may be different to each indoor unit according to combination.
  • Page 175 1-4. Example for unit selection with cooling load (1) Given condition 1) Design condition <Cooling: Indoor 20°C(WB), Outdoor 33°C(DB)> 2) Cooling load Location Room A Room B Room C Room D Room E Room F Load (kW) 3) Power supply unit: 3 Phase 380V 50Hz 4) Pipe length: 30m (2) Indoor unit selection Select the suitable capacity for condition of 'Indoor 20°C(WB), Outdoor 33°C(DB)' using...
  • Page 176 Ι Λ . Outdoor unit 2. Specification 2-1. 50Hz RVMC060GAM0 Model RVMC060GDM0 RVMC100GAM0 RVMC060GAM1 Power supply ø, V, Hz 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 Remark Cooling only Performance Capacity Cooling Btu/h 55000(7000~55000) 55000(7000~55000) 95500(7000~95500) 16.0(2.0~16.0) 16.0(2.0~16.0) 28.0(2.0~28.0)
  • Page 177 Model RVMH060GBM0 RVMH060GDM0 RVMH080GAM0 RVMH100GAM0 RVMH100GCM0 Power supply ø, V, Hz 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 Remark Heat pump Performance Capacity Cooling Btu/h 55000(7000~55000) 55000(7000~55000) 76000(7000~76000) 95500(7000~95500) 95500(7000~95500) 16.0(2.0~16.0) 16.0(2.0~16.0) 22.4(2~22.4) 28.0(2.0~28.0) 28.0(2.0~28.0)
  • Page 178 Ι Λ . Outdoor unit 2. Specification 2-2. 60Hz RVMC050CBM0 RVMC070FAM0 RVMC100FAM0 RVMH050CBM0 RVMH100FAM0 Model ø, V, Hz 1, 208~230, 60 3, 208~230, 60 3, 208~230, 60 1, 208~230, 60 3, 208~230, 60 Power supply Cooling only Heat pump Remark Performance 50000(7000~50000) 68000(7000~68000)
  • Page 179 MUF7201F1 Model ø, V, Hz 3, 380, 60 1, 220, 60 Power supply Cooling only Remark Super Cooler Performance 71000 Capacity (ISO) Cooling Btu/h 20.8 Heating Btu/h 60500 Capacity (SASO) Cooling Btu/h 17.7 Sound Level Cooling (Front View) Heating ZRD72KC-TF7 Power Compressor Model...
  • Page 180 Ι Λ . Outdoor unit 3. Functional parts and safety devices RVMC060GAM0 Item Code Name RVMC050CBM0 RVMC060GDM0 RVMC060GAM1 ZRD49KC-PFV ZRD72KC-TFD ZRD72KCE-TFD Motor output 3.7kW 4.5kW 4.5kW open temp. 120°C 145°C 145°C Compressor Compressor safety OLP trip current Crank case heater...
  • Page 181 Item Code Name MUF7201F1 RVMC070FAM0 RVMC100GAM0 RVMC100FAM0 ZRD72KC-TF7 ZRD72KC-TF5 ZRDT14MC-TFD ZRDU13MC-TF5 Motor output 5.5kW 5.5kW 4.2kW + 4.2kW 5.5kW + 4.3kW open temp. 155°C 175°C 120°C/145°C 175°C/160°C Compressor Compressor safety OLP trip current 110A 60A/48A 110A/80A Crank case heater model OSM1076SRC OSM1076SRC OSM4506SRC...
  • Page 182 Ι Λ . Outdoor unit 3. Functional parts and safety devices Item Code Name RVMH050CBM0 RVMH060GBM0 RVMH060GDM0 RVMH080GAM0 ZRD49KC-PFV ZRD72KC-TFD ZRD72KCE-TFD ZRDU13MC-TFD Motor output 4.5kW 4.5kW 4.2kW + 3.5kW 3.7kW open temp. Compressor 120°C 145°C 145°C 155°C Compressor safety OLP trip current Crank case heater model...
  • Page 183 Item Code Name RVMH100GAM0 RVMH100FAM0 ZRDT14MC-TFD ZRDU13MC-TF5 Motor output 4.2kW + 4.2kW 5.5kW + 4.3kW open temp. Compressor 155°C 155°C Compressor safety OLP trip current Crank case heater model OSME4506SRC OSME4508SRC Fan motor output 450W 450W Motor 150°C 150°C Safety thermostat 100°C 100°C Safety...
  • Page 184 Ι Λ . Outdoor unit 3. Functional parts and safety devices Item Code Name RVMH100GCM0 ZRDT14MCE-TFD Motor output 4.2kW + 4.2kW Compressor open temp. 155°C Compressor safety OLP trip current Crank case heater OSME4506SRC model Fan motor output 450W Motor 150°C Safety thermostat 100°C...
  • Page 185 4. Capacity table 4-1. 50Hz (1) Cooling TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 14.1 15.2 16.3 17.3 17.8 19.1 19.2 14.1 15.2 16.3 17.3 17.8 19.1 19.2 14.1 15.2 16.3...
  • Page 186 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 9.86 2.74 10.64 2.86 11.38 2.92 12.12 2.98 12.45 3.02 13.35 3.10 13.46 3.18 9.86 2.78...
  • Page 187 TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 24.6 26.6 28.4 30.3 31.1 33.4 33.7 10.4 24.6 26.6 28.4 30.3 31.1 33.4 33.7 10.6 24.6 26.6 28.4 30.3 31.1 33.4 33.7 10.8...
  • Page 188 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 17.25 5.39 18.62 5.62 19.91 5.74 21.20 5.85 21.79 5.93 23.36 6.45 23.56 7.30 17.25 5.47...
  • Page 189 (2) Heating TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Combination, Outdoor temperature %(Capacity index) ºC, DB ºC, WB 11.9 11.7 11.5 11.3 11.2 11.2 13.3 13.1 13.0 12.8 12.6 12.6 14.9 14.6 14.2 14.0 13.9 13.9 16.2 15.8...
  • Page 190 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Combination, Outdoor temperature %(Capacity index) ºC, DB ºC, WB 20.8 20.5 20.1 19.8 10.1 19.5 10.4 19.5 10.4 23.3 23.0 22.8 22.4 10.4...
  • Page 191 4-2. 60Hz (1) Cooling TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 12.8 13.8 14.7 15.7 16.1 17.3 17.4 12.8 13.8 14.7 15.7 16.1 17.3 17.4 12.8 13.8 14.7 15.7 16.1 17.3...
  • Page 192 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 8.93 2.16 9.64 2.25 10.31 2.29 10.98 2.34 11.28 2.37 12.10 2.43 12.20 2.49 8.93 2.19...
  • Page 193 TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 17.6 19.0 20.3 21.6 22.2 23.8 24.0 17.6 19.0 20.3 21.6 22.2 23.8 24.0 17.6 19.0 20.3 21.6 22.2 23.8 24.0 17.6 19.0 20.3...
  • Page 194 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 12.32 3.31 13.30 3.45 14.22 3.52 15.15 3.59 15.57 3.64 16.69 3.73 16.83 3.83 12.32 3.35...
  • Page 195 TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 18.3 19.8 21.1 22.5 23.1 24.8 25.0 18.3 19.8 21.1 22.5 23.1 24.8 25.0 18.3 19.8 21.1 22.5 23.1 24.8 25.0 18.3 19.8 21.1...
  • Page 196 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 12.81 3.48 13.83 3.63 14.79 3.70 15.75 3.78 16.19 3.83 17.35 3.93 17.50 4.03 12.81 3.53...
  • Page 197 TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 24.6 26.6 28.4 30.3 31.1 33.4 33.7 24.6 26.6 28.4 30.3 31.1 33.4 33.7 24.6 26.6 28.4 30.3 31.1 33.4 33.7 24.6 26.6 28.4...
  • Page 198 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, WB) Combination, Outdoor %(Capacity temperature index) (ºC, DB) 17.25 5.39 18.62 5.62 19.91 5.74 21.20 5.85 21.79 5.93 23.36 6.08 23.56 6.24 17.25 5.47...
  • Page 199 (2) Heating TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Combination, Outdoor temperature %(Capacity index) ºC, DB ºC, WB 10.6 10.4 10.2 10.1 11.8 11.7 11.6 11.4 11.2 11.2 13.3 13.0 12.6 12.5 12.3 12.3 14.4 14.1 13.6 13.3...
  • Page 200 Ι Λ . Outdoor unit 4. Capacity table TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Combination, Outdoor temperature %(Capacity index) ºC, DB ºC, WB 20.8 20.5 20.1 19.8 10.1 19.5 10.4 19.5 10.4 23.3 23.0 22.8 22.4 10.4...
  • Page 201 5. Dimension 5-1. Upward (2-FAN) Unit : mm Ι Λ...
  • Page 202 Ι Λ . Outdoor unit 5. Dimension 5-2. Onward Unit : mm Ι Λ Ι Λ...
  • Page 203 5-3. Upward (1-FAN) Unit : mm Ι Λ...
  • Page 204 Ι Λ . Outdoor unit 5. Dimension 5-4. Upward(Super cooler) Unit : mm Ι Λ...
  • Page 205 6. Refrigerant system diagram 6-1. Cooling only 050/060/070/720 motor motor super cooler solenoid valve (HGBV) capillary tube temperature sensor temperature sensor high pressure switch heat exchanger solenoid valve (PWM) digital scroll temperature com- sensor pressor solenoid solenoid receiver valve (VBV) valve (LBV) temperature sensor capillary tube...
  • Page 206 Ι Λ . Outdoor unit 6. Refrigerant system diagram 080/100 motor solenoid valve (HGBV) capillary tube temperature sensor high pressure switch high pressure sensor heat exchanger solenoid valve Oil separator temperature (PWM) sensor cond out sensor temper- ature sensor digital fixed scroll scroll...
  • Page 207 (3) Main parts status 1) Digital scroll compressor The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps. 2) Accumulator To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back). 3) Receiver To reduce the noise by flowing the high pressure liquid refrigerant to the high pressure pipe and to control the amount of refrigerant during the individual operation of indoor unit.
  • Page 208 Ι Λ . Outdoor unit 6. Refrigerant system diagram 6-2. Heat pump 050/060 motor motor solenoid valve (HGBV) capillary tube temperature high pressure sensor temperature switch sensor high pressure 4-way sensor valve (4-W/V) heat exchanger electronic expansion valve(EEV) filter cond out sensor solenoid valve...
  • Page 209 080/100 motor solenoid valve (HGBV) capillary tube temperature high pressure sensor high pressure switch sensor 4-way valve (4-W/V) heat exchanger electronic expansion valve(EEV) oil separator filter temperature sensor cond out sensor solenoid temper- ature valve fixed digital sensor (PWM) check valve scroll scroll (C/V)
  • Page 210 Ι Λ . Outdoor unit 6. Refrigerant system diagram (3) Main parts status 1) Digital scroll compressor The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps 2) Accumulator To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back). 3) Receiver To reduce the noise by flowing the high pressure liquid refrigerant to the high pressure pipe and to control the amount of refrigerant during the individual operation of indoor unit.
  • Page 211 13) 4-way valve (4-W/V) It enables the change between cooling and heating by reversing the flow direction of refrigerant. 14) Electronic expansion valve (EEV) By sensing suction temperature and low pressure, controls the suction super heat and mass flow of refrigerant. 15) Check valve (C/V) To reduce the loss of pressure at the electronic expansion valve while cooling and to prevent the over-load of the compressor.
  • Page 212 Ι Λ . Outdoor unit 7. Electric circuit diagram 7-1. Cooling only 050/060/072 Ι Λ...
  • Page 213 070F Ι Λ...
  • Page 214 Ι Λ . Outdoor unit 7. Electric circuit diagram 080/100 Ι Λ...
  • Page 215 100F Ι Λ...
  • Page 216 Ι Λ . Outdoor unit 7. Electric circuit diagram 7-2. Heat pump 050/060 Ι Λ...
  • Page 217 080/100 Ι Λ...
  • Page 218 Ι Λ . Outdoor unit 7. Electric circuit diagram 100F Ι Λ...
  • Page 219 8. Consideration for outdoor unit selection 8-1. Change of capacity depending on refrigerant piping length (1) Change of cooling capacity 1) 5 ~ 7 HP 95.0% 94.0% 92.5% 91.0% 89.5% 88.0% 86.5% 97.0% 98.5% 100% Height difference (m) 100% 97.0% 91.0% 94.0% 88.0%...
  • Page 220 Ι Λ . Outdoor unit 8. Consideration for outdoor unit selection (2) Change of heating capacity 1) 5 ~ 7 HP Height difference (m) Piping length (m) Refrigerant piping length and performance range correction following the height difference should be extracted from the graph (minus height difference means that the outdoor unit is installed below the indoor unit).
  • Page 221 8-2. Condition of operating restriction (1) Cooling (2) Heating Only for the Outdoor Outdoor Middle East temperature (DB) temperature (WB) Operating Envelope Operating Envelope Cold-oriented type Indoor temperature(WB) Indoor temperature(DB) The reliability of air conditioner is preserved till the outdoor temperature drops below -15 C even though the air conditioner is a cold-oriented type, but...
  • Page 222 Ι Λ . Outdoor unit 9. Noise level 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 Front 10.0 Back NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 80.0 70.0 NC-65 60.0 NC-60 50.0...
  • Page 223 070/072 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 Front 10.0 Back NC-15 1000 2000 4000 8000 Octave band center frequency(Hz) 080/100 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0...
  • Page 224 Ι Λ . Outdoor unit 10. Options Optional Items Capacity Design Discharge Interface Centralized Function Refnet (HP) duct module controller controller joint MDF-45A 6.0 ~ 7.5 MIM-B00 MCM-A200 MCM-A100 (2 FAN) MXJ-0906A MDF-46A MXJ-1206A 5.0 ~ 6.0 MIM-B00 MCM-A200 MCM-A100 MXJ-2212A (2 FAN) MXJ-3112A...
  • Page 225: Pipe Selection

    Installation 1. Product 7. Wiring 1-1. Preparation for installation 7-1. Overall system configuration 1-2. Deciding on where to install 7-2. Cable specification for outdoor unit the air conditioner 7-3. Connection cord specification 1-3. Space requirements for 7-4. Wiring diagram the air conditioner 7-5.
  • Page 226: Preparation For Installation

    . Installation 1. Product 1-1. Preparation for installation When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account. (1) General Do NOT install the air conditioner in a location where it will come into contact with the following elements: Combustible gases Saline air Machine oil...
  • Page 227: Deciding On Where To Install The Air Conditioner

    1-2. Deciding on where to install the air conditioner (1) Indoor unit There must be no obstacles near the air inlet and outlet. Install the indoor unit on a ceiling that can support its weight. Maintain sufficient clearance around the indoor unit. Make sure that the water dripping from the drain hose runs away correctly and safely.
  • Page 228 . Installation 1. Product 1-3. Space requirements for the air conditioner (1) Indoor unit 1) 1-way cassette type 2) 4-way cassette type 3) Duct type (Low silhouette) You must have 5mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the vibration of indoor unit may bother the user.
  • Page 229 4) Duct type (Built-in) You must have 5mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the vibration of indoor unit may bother the user. 5) Duct type (High pressure) You must have 5mm or more space between the ceiling and the bottom of indoor unit.
  • Page 230 . Installation 1. Product 7) Floor standing type Top view Side view 60cm or more 50cm or more Air outlet Air inlet 8) Ceiling type 100cm or more...
  • Page 231 (2) Outdoor unit 1) Onward Strong wind Roof top 60cm or more 50cm or more Space for piping 50cm or more and wining Space for piping 30cm or more 30cm or more and wining 30cm or more The air inlet faces toward the wall. The air outlet faces toward the wall.
  • Page 232 . Installation 1. Product 3) Upward (8.0HP or more) The outdoor unit is placed higher than the outdoor wall. a. Installation for 1 line Unit : mm 800 or less Front 100 or 200 or 200 or 200 or 200 or more more more...
  • Page 233 When the outdoor unit is placed lower than the outdoor wall. a. The case of installing gallery - Keep the intake fan speed under 1.5m/s from the gallery. - Make the height of discharge duct (HD) be H-h. Unit : mm Discharge duct 1000 or more Front...
  • Page 234 . Installation 1. Product 1-4. Accessories (1) 1-way cassette type Pattern sheet Flexible hose Insulation Installation Rubber (8) drain hose (1) manual (1) (2) 4-way cassette type Pattern sheet Insulation Insulation (2) Insulation Insulation pipe Insulation cover drain (1) cover band (1) drain hose (2) Installation Cable-tie (5)
  • Page 235 (4) Duct type (Built-in) Pattern sheet Insulation Insulation (2) Insulation Insulation pipe Insulation cover drain (1) cover band (1) drain hose (2) Cable-tie (5) Flexible hose Insulation Owner’s Installation drain sub (1) Instructions (1) manual (1) (5) Duct type (High pressure) Pattern sheet Insulation A Insulation B...
  • Page 236 . Installation 1. Product (7) Floor standing type (8) Ceiling type...
  • Page 237 1-5. Installation (1) Indoor unit (Example; 4-way cassette type) 1) Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity.
  • Page 238 . Installation 1. Product (2) Outdoor unit The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration, particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to an appropriate support(wall or ground).
  • Page 239 2. Panel 2-1. 1-way cassette type (1) Accessories M4x12 M5x16 bolt (4) tapped screw Wireless remote Battery (2) STS 2S-2x10 Remote control Owner’s Installation controller (1) tapped screw holder (1) instructions (1) manual (1) (2) Installation 1) Open the front grille by pushing tabs on the grille. 2) Remove safety clips to open the grille completely.
  • Page 240 . Installation 2. Panel 4) Install the air flow blade. 4-1 Fix the right part of the blade to the indoor unit. 4-2 Fix the other side of the blade. IMPORTANT If the direction is incorrect, the blade will not be inserted smoothly.
  • Page 241 2-2. 4-way cassette type (1) Accessories Wireless remote Battery (2) Remote control Owner’s Owner’s controller (1) holder (1) instructions (1) instructions (1) 4x12 Tapped Bolt (4) Air blocking kit (1) screw (2) Must be separately purchased (2) Installation 1) Open the electrical component box cover removing the screws. 2) Install the panel using two hooks on the both sides of the indoor unit.
  • Page 242 . Installation 2. Panel 2-3. Duct type (Built-in) (1) Accessories Tapped screw Fixing bracket (1 or 2) (2) Installation 1) Separate the front grille from the panel. 1-1 Push the lever of front grille right and left to lift it up and then open it.
  • Page 243 3) Attach the panel to the indoor unit, then push it to right or left to secure the panel. Narrow side of hole on the panel must be inserted between the screw and the indoor unit. 4) Adjust the location of panel so that there is no gap between the panel and ceiling, then tighten the screw completely.
  • Page 244 . Installation 3. Connecting the indoor unit refrigerant pipe There are two refrigerant pipes of differing diameters: Refrigerant oil A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper pipe must be clean & has no dust. 1) Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually and then with a wrench, a spanner applying the...
  • Page 245 Cutting/Flaring the Pipes 1) Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder). 2) If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe.
  • Page 246: Drain Hose Installation

    . Installation 4. Drain hose installation (Example;4-way cassette type) Care must be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly drained outside. 1) Insert the flexible hose to the drain hose port. Attach the drain hose to the drain hose port with an adhesive for PVC and tape to prevent water leaks, then secure the hose with Drain hose...
  • Page 247 If a concentrated drain hose is installed, refer to the figure below. Drain clamp Air ventilation Concentrated drain hose Testing the drainage You should test the drainage after completing the installation. Prepare a little water about 2.0 liters. 1) Remove two screws on the cover water supply intake and pull out the cover.
  • Page 248 . Installation 5. Drain pump installation-optional (Example;Low-silhouette duct type) 5-1. Accessories Drain pump & M4x12 Cable-tie (2) Cable clamp Float switch (1) Tapped screw 5-2. Installation (1) Connect the cable to the electrical component box as shown at the figure. Connect the drain pump cable to yellow terminal(CN74) and the float switch to black terminal(CN51).
  • Page 249 6. Electronic expansion valve kit 6-1. Built-in type (Example;1-way cassette type) (1) Connect a strainer to the "IN" pipe and fix it. (2) Fix the electronic expansion valve kit with 2 screws(TH4x12) as shown at the figure. (3) Connect the "OUT" pipe to the liquid refrigerant pipe. (4) Insulate the connection piping.
  • Page 250 . Installation 6. Electronic expansion valve kit 6-2. Distributor kit type (1) Preparation for installation Unit : mm...
  • Page 251 (2) Electronic expansion valve kit installation 1) Connection of refrigerant piping & Installation Decide an installation place that can support the electronic expansion valve kit. Connect the “IN” refrigerant pipe to the outdoor unit. Connect the “OUT” refrigerant pipe to each indoor unit (A, B and C).
  • Page 252 . Installation 6. Electronic expansion valve kit 2) Wiring & Assigning address Room A Room B Another distributor kit Outdoor unit Room C Connect the AC power cable and communication cable from the outdoor unit to terminal, then connect the cable to another electronic expansion valve kit. Connect the AC power cable and communication cable to each indoor unit (A, B and C).
  • Page 253 3) Function of Display The numbers which is displayed on left are the status of indoor unit checking status through communication with same outdoor unit. (If it indicates 1, 3 and 7, that means the ADDRESS of indoor unit is set to 1, 3 and 7.) The numbers which is displayed on right indicate the ADDRESS of SW51, SW52 and SW53 in sequential.
  • Page 254 . Installation 7. Wiring Caution All wiring and parts shall be the rated ones. For details of wiring, refer to the circuit diagram attached onto the outdoor unit. The electrical work shall be performed by the qualified electrical worker. The circuit diagram for wiring shows only the concept and so the details for actual work is not described. This air conditioner is consist of 3 phase 4 wire system and so the main circuit breaker to block the power shall be installed in the integrated manner.
  • Page 255 7-2. Cable specification for outdoor unit Power Supply Commu- nication 3 Phase Single Phase Earth Outdoor unit Cable Cable Power Max/Min Power Power Max/Min Power (HOS-RN- MCCB Cable Length MCCB F, 2wires) Supply Supply Cable 208- 2.0mm 253/187 230V~ CV, 3Wire /60Hz 4.0mm HOS-RN-F,...
  • Page 256: Wiring Diagram

    . Installation 7. Wiring 7-3. Connection cord specification Power supply (1 phase) Communication cable Home server Earth wire (VCTF, 2wires) (VCTF, 2wires) Power supply Max/Min (V) Power cable 220V / 60Hz 2.0mm 1.6mm 220-240V/50Hz ± 10% 0.75~1.25mm 0.75~1.25mm (CV, 2wires) (IV, 1wire) 208-230V/60Hz The power supply cable shall be connected to the power supply terminal and shall be fixed with clamp as in the following figure.
  • Page 257 7-5. Connection cord wiring diagram Indoor unit 1 Indoor unit 2 Indoor unit 3 Outdoor unit 2.5HP Outdoor unit - Max. length of communication cable : 120m - Whole length of cable : 240m - Allowable branches : 10 The communication cable shall be wired as follows: When the communication cable exceeds the specified length, the operation of air conditioner may be impossible due to the trouble of communication between indoor and outdoor unit.
  • Page 258 . Installation 7. Wiring 7-7. Communication cable connection (1) Correct connection Outdoor unit Indoor unit Wired remote controller...
  • Page 259 (2) Typical wiring error 1) Star wiring connection to some of the indoor units Outdoor unit Indoor unit Wired remote controller...
  • Page 260 . Installation 7. Wiring 2) Star wiring connection to every indoor units Outdoor unit Indoor unit Wired remote controller...
  • Page 261 3) Reverse wiring between indoor and outdoor units Outdoor unit Indoor unit Wired remote controller Reverse...
  • Page 262 . Installation 7. Wiring 4) Disconnection between indoor and outdoor units Outdoor unit Indoor unit Wired remote controller Disconnection...
  • Page 263 5) Reverse wiring between indoor units Outdoor unit Indoor unit Wired remote controller Reverse...
  • Page 264 . Installation 7. Wiring 6) Disconnection between indoor units Outdoor unit Indoor unit Wired remote controller Disconnection...
  • Page 265 8. Piping and refnet joint selection 8-1. Examples of using only Refnet joint (during eight rooms installation) Outdoor unit 8-2. Examples of using both Refnet joint and distributor kit (during eight rooms installation) Outdoor unit Distributor kit...
  • Page 266 . Installation 8. Piping and refnet joint selection 8-3. Limitation when piping is installed by using only Refnet joint (during six rooms installation) Outdoor unit Outdoor unit 5.0HP 6.0HP 7.0/7.5HP 8.0/10.0HP Item Actual length Max. Distance of the ex) In case of 10 horse power a+b+c+d+e+f ≤ 100m allowable remotest indoor unit Equivalent...
  • Page 267 8-4. Requirement when piping is installed using simultaneously both refnet joint and contributor kit (during six rooms installation) Outdoor unit Distributor kit Outdoor unit 5.0HP 6.0HP 7.0/7.5HP 8.0/10.0HP Item Actual length Max. Distance of the ex) In case of 10 horse power a+b+c+d+j ≤ 100m allowable remotest indoor unit Equivalent...
  • Page 268 . Installation 8. Piping and refnet joint selection 8-5. Pipe selection Capacity of outdoor unit 5.0HP 6.0HP 7.0/7.5HP 8.0/10.0HP Outdoor unit ~ The first refnet joint piping Liquid Pipe ø9.52mm X t0.8 ø12.70mm X t0.8 Piping size Gas Pipe ø19.05mm X t1.2 ø22.22mm X t1.2 ø25.40mm X t1.2 ø28.60mm X t1.2 Refnet joint ~ Refnet joint piping less than 16000W ø9.52mm X t0.8...
  • Page 269 Equivalent length calculation method equivalent length = actual pipe length + number of elbows + number of elbows X equivalent length of each elbows + number of oil traps X equivalent length of each oil trap Type Elbow Oil Trap Piping diameter (mm) 9.52 0.18...
  • Page 270 . Installation 8. Piping and refnet joint selection 8-6. Refnet joint selection (1) Selection method of first refnet joint from the outdoor unit The first refnet joint (joint A) from the outdoor unit shall be selected according to the outdoor unit model. Length (mm) Diameter (mm) Refnet joint model...
  • Page 271: Recovery Of Refrigerant

    9. Charge/recovery of refrigerant 9-1. Refrigerant charging (1) Outdoor unit is charged with refrigerant when being delivered but additional refrigerant shall be charged for some part of system. (2) After completion of vacuum, keep the following instructions to fill the refrigerant into the service port.
  • Page 272 . Installation 9. Charge/recovery of refrigerant 9-2. Additional refrigerant amount calculation method (1) The amount of refrigerant filled in the outdoor when the product is delivered (on the base of piping 10 m) (2) Additional amount of refrigerant as per the pipe diameter and length (liquid pipe based) 12.70( 12.70(...
  • Page 273 9-3. Recovery of refrigerant (1) Close the service valve of liquid side and then press the refrigerant recovery button on outdoor PCB (2) When the low pressure is getting lower enough, close the service valve to press the refrigerant recovery button again or press key 3. Pressing the button stops the compressor.
  • Page 274: Cautions For Operation

    . Installation 10. Testing operation Cautions for operation Put the power 6 hours before initial operation so that the crank case heater may be heated. When doing the retry of initial operation after main power off, start the operation 2 and half hours after power on. If the heater is not heated, the operation can not be started for 2 hours after power on for the protection of compressor.
  • Page 275: Cooling Mode

    (8) If the preheating of compressor is completed, the communication is performed between indoor unit connected and options. It is the normal at the time when the address on the right display is shown as many as shown on the left side display. (9) Check through the PC connected with outdoor unit whether the data is correct from temperature sensor and electronic expansion valve.
  • Page 276: Key Functions

    . Installation 10. Testing operation KEY functions (1) RVMC060GAM0(1) Press times Key 1 Key 2 Key 3 Key 4 Heating refrigerant charge Cooling refrigerant charge Reset View Mode Heating test operation Cooling test operation Pump down (2) The other models 1) Display 2) Key Dis 1...
  • Page 277 4) VIEW mode According to the number of pushes on KEY 4, displays the proper data, and if the model contains no content to display, display only the number of pushes on SEG 1. 4-1 Input 1 time: Displays the data of high pressure (displays down to three decimal places) Ex.) In the case of the high pressure is 21.2kg/cm SEG 1: 1 flickers SEG 2, 3, 4: each of them, displays 2, 1, 2...
  • Page 278 . Installation 11. Cautions for refrigerant leaks 11-1. Introduction The DVM system, like most other air conditioning systems, uses R-22 as its refrigerant. R-22 itself is an entirely safe non-toxic, non-combustible refrigerant but care must nevertheless be taken to ensure that the air conditioning facilities are installed in a room which is sufficiently large to avoid a *dangerous concentration of refrigerant gas in the unlikely event of a serious leak in the system.
  • Page 279 11-2. Procedure for checking dangerous Concentration Check the dangerous concentration in accordance with steps 1~4 below and take whatever action is necessary. (1) Calculate the amount of refrigerant(kg) charged to each system separately. (Amount of refrigerant in a Total amount of refrigerant(kg) (Additional charging amount) = single indoor unit system) in the system...
  • Page 280 . Installation 11. Cautions for refrigerant leaks 3) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target. Outdoor unit Ventilator Indoor unit Smallest Second smallest room...
  • Page 281 (4) Dealing with situations where the result exceeds the dangerous concentration level. Where the installation of a facility results in a concentration in excess of the dangerous concentration level then it may be necessary to revise the system design to some extent or else take one of the fol- lowing courses of action: <Action 1>...
  • Page 282 DB98-03759A(2) 2002.06.

Table of Contents