8-4. Requirement when piping is installed using simultaneously both refnet
joint and contributor kit
Outdoor unit
b
a
e
Item
Max.
Distance of the
allowable
remotest indoor unit
length
from the outdoor unit
Height difference between outdoor unit
Max.
and indoor unit (m) = H1(the figures in the
allowable
parenthesis is applied when the outdoor
height
unit is installed below the indoor unit)
difference
Height difference between indoor unit = H2
Allowable length after branching
N N
o o
t t
e e
The distributor kit is applicable to indoor units that are not embedded with electronic expansion
N N
o o
t t
e e
valve, that is, 1-way cassette or Wall-mounted type, and it has less coolant noise compared to
the electronic expansion valve kit of embedded type. Therefore we recommend the product to
be used in study rooms or private offices where noise control is required.
1) Equivalent length means a calculated value of the actual length plus pressure loss caused by piping curve.
For instance, the equivalent in the case of 10 horse power should be 125 meters (The detailed calculation
of equivalent length should be referenced in pages V-43).
(during six rooms installation)
c
d
Distributor kit
g
f
Outdoor unit
5.0HP
70
Actual length
ex) In case of 10 horse power a+b+c+d+j ≤ 100m
(m)
Equivalent
87
length (m)
1)
ex) In case of 10 horse power ≤ 125m
30 (30)
The distance from the first refnet joint to the indoor unit :
Between distributor kit and indoor unit ≤ 30m
43
h
i
6.0HP
7.0/7.5HP
50 (40)
15m
ex) b+c+d+j ≤ 30m, b+c+d+h ≤ 30m
H1
j
H2
8.0/10.0HP
100
125