Samsung RVMC060GDM0 Technical Manual page 105

Dv m air conditioner
Table of Contents

Advertisement

ΙΙΙ
. Indoor unit
4. Capacity table
(2) Heating
Outdoor temperature
Unit Size
020
032
040
16.0
(ºC)
TC
DB
WB
kW
-15
-14
1.45
-12
-13
1.63
-10
-11
1.83
-7
-8
1.98
-5
-6
2.13
-3
-4
2.24
0
-1
2.33
3
2.2
2.38
5
4.1
2.46
7
6
2.53
9
7.9
2.57
11
9.8
2.57
13
12
2.57
15
14
2.57
-15
-14
2.31
-12
-13
2.59
-10
-11
2.91
-7
-8
3.15
-5
-6
3.40
-3
-4
3.57
0
-1
3.71
3
2.2
3.78
5
4.1
3.92
7
6
4.03
9
7.9
4.10
11
9.8
4.10
13
12
4.10
15
14
4.10
-15
-14
2.8
-12
-13
3.2
-10
-11
3.6
-7
-8
3.9
-5
-6
4.2
-3
-4
4.4
0
-1
4.6
3
2.2
4.6
5
4.1
4.8
7
6
4.9
9
7.9
5.0
11
9.8
5.0
13
12
5.0
15
14
5.0
ΙΙΙ
Indoor temperature (ºC, DB)
18.0
20.0
TC
TC
kW
kW
1.43
1.40
1.61
1.59
1.78
1.74
1.94
1.87
2.05
1.98
2.16
2.08
2.24
2.20
2.33
2.20
2.38
2.20
2.38
2.20
2.38
2.20
2.38
2.20
2.38
2.20
2.38
2.20
2.28
2.23
2.56
2.53
2.84
2.76
3.08
2.98
3.26
3.14
3.43
3.31
3.57
3.50
3.71
3.50
3.78
3.50
3.78
3.50
3.78
3.50
3.78
3.50
3.78
3.50
3.78
3.50
2.8
2.7
3.1
3.1
3.5
3.4
3.8
3.7
4.0
3.9
4.2
4.1
4.4
4.3
4.6
4.3
4.6
4.3
4.6
4.3
4.6
4.3
4.6
4.3
4.6
4.3
4.6
4.3
48
TC : Total capacity
22.0
24.0
TC
TC
kW
kW
1.39
1.36
1.56
1.54
1.72
1.69
1.83
1.78
1.94
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.02
1.89
2.21
2.17
2.49
2.45
2.73
2.70
2.91
2.84
3.08
3.01
3.22
3.01
3.22
3.01
3.22
3.01
3.22
3.01
3.22
3.01
3.22
3.01
3.22
3.01
3.22
3.01
3.22
3.01
2.7
2.7
3.1
3.0
3.4
3.3
3.6
3.5
3.8
3.7
4.0
3.7
4.0
3.7
4.0
3.7
4.0
3.7
4.0
3.7
4.0
3.7
4.0
3.7
4.0
3.7
4.0
3.7

Hide quick links: