Samsung RVMC060GDM0 Technical Manual page 107

Dv m air conditioner
Table of Contents

Advertisement

ΙΙΙ
. Indoor unit
4. Capacity table
Outdoor temperature
Unit Size
128
16.0
(ºC)
TC
DB
WB
kW
-15
-14
9.1
-12
-13
10.2
-10
-11
11.5
-7
-8
12.4
-5
-6
13.4
-3
-4
14.1
0
-1
14.6
3
2.2
14.9
5
4.1
15.5
7
6
15.9
9
7.9
16.1
11
9.8
16.1
13
12
16.1
15
14
16.1
ΙΙΙ
Indoor temperature (ºC, DB)
18.0
20.0
TC
TC
kW
kW
9.0
8.8
10.1
10.0
11.2
10.9
12.1
11.8
12.8
12.4
13.5
13.0
14.1
13.8
14.6
13.8
14.9
13.8
14.9
13.8
14.9
13.8
14.9
13.8
14.9
13.8
14.9
13.8
50
TC : Total capacity
22.0
24.0
TC
TC
kW
kW
8.7
8.6
9.8
9.7
10.8
10.6
11.5
11.2
12.1
11.9
12.7
11.9
12.7
11.9
12.7
11.9
12.7
11.9
12.7
11.9
12.7
11.9
12.7
11.9
12.7
11.9
12.7
11.9