Wiring Diagram - Samsung RVMC060GDM0 Technical Manual

Dv m air conditioner
Hide thumbs

Advertisement

Table of Contents
. Installation
7. Wiring
7-3. Connection cord specification
Power supply (1 phase)
Power supply
220V / 60Hz
220-240V/50Hz
208-230V/60Hz
The power supply cable shall be connected to the power supply terminal and shall be fixed with clamp as in the following figure.
The unbalance of power shall be within 2% of power supply rating.
- If the power supply unbalance is great, the lifetime of condenser is shortened.
- If the power supply unbalance exceeds 4%, the indoor unit stops and error mode displays.

7-4. Wiring diagram

When using ELBs for 3 phase and 1 phase
MCCB
Single
ELB
ELB
Phase
MCCB
MCCB
When using ELB for 3 phase 4 wires
Power Supply
MCCB
3 Phase
ELB
4 Wires
MCCB
Max/Min (V)
Power cable
2.0mm
± 10%
(CV, 2wires)
Power Supply
3 Phase
Electrical component box
3 Wires
Indoor Unit
Case 2
Electrical component box
Indoor Unit
Communication cable
Earth wire
(VCTF, 2wires)
2
1.6mm
0.75~1.25mm
(IV, 1wire)
Case 1 Cut off the part A and B
Part B
Part A
Cable
clamp
Communication
Connection cord
Cable
Cable
clamp
Connection cord
Communication
Cable
Cable
clamp
Communication
Connection cord
Cable
32
Home server
(VCTF, 2wires)
2
0.75~1.25mm
Single
Phase
AC220V
3 Phase
Power Cable
Single
Phase
AC220V
3 Phase
Power Cable
3 Phase
Power Cable
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents