Samsung RVMC060GDM0 Technical Manual page 268

Dv m air conditioner
Table of Contents

Advertisement

. Installation
8. Piping and refnet joint selection
8-5. Pipe selection
Capacity of outdoor unit
Piping size
Liquid
Capacity limit of
pipe
rear indoor unit
Gas
Capacity limit of
pipe
rear indoor unit
Liquid
Capacity limit of
pipe
rear indoor unit
Gas
Capacity limit of
pipe
rear indoor unit
5.0HP
Outdoor unit ~ The first refnet joint piping
Liquid Pipe
ø9.52mm X t0.8
Gas Pipe
ø19.05mm X t1.2 ø22.22mm X t1.2 ø25.40mm X t1.2 ø28.60mm X t1.2
Refnet joint ~ Refnet joint piping
less than 16000W
more than 16000W
less than 9000W
9000W~16000W
16000W~21000W
more than 21000W
Refnet joint ~ Indoor unit piping
less than 4700W
more than 4700W
less than 4700W
4700W~8500W
more than 8500W
44
6.0HP
7.0/7.5HP
ø12.70mm X t0.8
ø9.52mm X t0.8
-
ø12.70mm X t0.8
ø15.88mm X t1.0
ø19.05mm X t1.2
-
ø25.40mm X t1.2
-
ø6.35mm X t0.7
ø9.52mm X t0.8
ø12.70mm X t0.9
ø15.88mm X t1.0
ø19.05mm X t1.2
8.0/10.0HP
ø28.60mm X t1.2

Hide quick links: