Samsung RVMC060GDM0 Technical Manual page 231

Dv m air conditioner
Table of Contents

Advertisement

(2) Outdoor unit
1) Onward
60cm or more
30cm or more
The air inlet faces toward the wall.
2) Upward (7.5HP or less)
If there is no obstacle around the unit...
300 or more
100 or more
Front
500
or more
300 or more
Front
100 or more
500
or more
Max. height of obstacle
- Front side : 1500mm or less
- Air inlet side : 500mm or less
- Right/Left side : No limit
If there is an obstacle around the unit...
If an obstacle in front of the outdoor unit is higher than
1500mm, the half of additional height should be
added to the S1.
If an obstacle behind the outdoor unit is higher than 500mm,
the half of additional height should be added to the S2.
Strong wind
Roof top
50cm or more
Space for piping
and wining
300 or more
100 or
100 or
500 or
more
more
more
100 or more
100 or
100 or
more
more
500 or
more
7
50cm or more
Space for piping
30cm or more
30cm or more
The air outlet faces toward the wall.
Unit : mm
100 or
100 or
100 or
more
more
more
Front
100 or
200 or
200 or
more
more
more
Front
S1
and wining
Unit : mm
S2

Hide quick links:

Advertisement

Table of Contents
loading