4 Performing Power-On and Power-Off Commissioning
Connecting the Power Cable of the Cabinet
4a
NOTE
• The 42 U cabinet connects to the mains supply cable through an industrial connector.
• The mains supply cable is prepared by customers based on the electrical specifications of
the external mains power distribution system.
Electrical specifications for the external mains power distribution system
Parameter
Input voltage
Maximum input current
Input circuit breaker
Tips
If the industrial connector fails to route through the cable hole
at the top of the cabinet, pull the two positioning pins at the top
of the cabinet inwards simultaneously with both hands to raise
the cabinet cover.
After routing the industrial connector through the cable hole,
pull the positioning pins inwards again with both hands to close
the cabinet cover. Then release your hands to secure the pins.
Value
176 V to 264 V AC
32 A
32 A/1 P
Connect to the mains
power system
45
Remarks
Connect with an industrial connector
complying with IEC standards.