AEG Protect C.1000 Operating Instructions Manual page 42

Hide thumbs Also See for Protect C.1000:
Table of Contents

Advertisement

42
Description
Adjustable parameters
Control
[enabled], [disabled]
commands
If enabled, control commands are
from serial port
accepted through Serial, USB port
and cards in the communication slot,
else control is restricted to the LCD
panel of the UPS.
[200V], [208V], [220V], [230V],
Output
[240V], [auto-sensing]
voltage
Setting only available in
UPS stand-by mode.
[50Hz], [60Hz], [auto-sensing]
Output
Setting only available in
frequency
UPS stand-by mode.
Load alarm
[10%], [20%], [30%], ... [100%]
level
NOTE: The level can be set in 10%
(Overload)
increments so a possible overload is
detected early.
Power strategy [High performance mode (normal)],
[Economical mode (ECO)],
[Converter mode]
Setting only available in
UPS stand-by mode.
Start w/o mains [enabled] [disabled]
cold Start
Site wiring
[enabled], [disabled]
fault alarm
Presetting
enabled
auto-sensing
auto-sensing
100%
normal
enabled
disabled