Description
Adjustable parameters
External battery
Configures the amount of
modules
external battery units
Battery charged
[0%], [10%], [20%], ...[100%]
% to restart
On battery operation the UPS output
is turned off as soon as the battery
capacity is below the selected level.
[enabled], [disabled]
Automatic
battery tests
[daily], [weekly], [monthly]
Periodic
battery test
Automatic battery tests run according to "periodic battery test", unless
disabled. During the test, the UPS transfers to Battery mode and
discharges the batteries approximately 10 seconds under the existing
load.
The "UPS on Battery" notice and the "Battery Low" alarm do not activate
during a battery test.
For automatic battery tests to run:
The "Automatic Battery Test" setting must be enabled.
The UPS must be in Normal mode, with no active alarms.
The battery system being tested must have sufficient reserve capacity.
With reference to the input voltage, the Bypass voltage window must
be within the range of tolerances.
43
Presetting
<0>
0 %
enabled
weekly