11.

STORAGE, DISMANTLING AND DISPOSAL

11.1 STORAGE

Long storage times without charging or discharging the battery at regular
intervals may lead to permanent damage of the battery..
Long storage times without charging or discharging the battery at regular
intervals may lead to permanent damage of the battery.
If the battery is stored at room temperature (20° C to 30° C) it will
automatically discharge at a rate of 3 - 6% per month due to internal
reactions. Storing the battery at temperatures above room temperature
should be avoided. A high storage temperature also means greater
battery self-discharge. Batteries that are stored at room temperature
should be recharged every six months to maintain their full capacity and
service life.
Connect PROTECT C to the mains before putting it into storage, in order
to make sure that the battery is fully charged. The charging time should
at least match the time specified in chapter 10.1 battery charging.

11.2 DISMANTLING

The system is dismantled in reverse order of the installation instructions.

11.3 DISPOSAL

In the interest of environmental protection and recycling, please dispose
of the individual system components in accordance with the regulations
and legal guidelines when permanently taking the system out of
operation. Please consider that infringements to these regulations may
result in civil or criminal prosecution.
Disposal of old electrical & electronic equipment (applicable in
the European Union and other European countries with separate
collection systems).