Huawei SUN2000-55KTL-HV-D1 User Manual page 94

Sun2000-55ktl; sun2000-60ktl series
Hide thumbs Also See for SUN2000-55KTL-HV-D1:
Table of Contents

Advertisement

SUN2000-(55KTL, 60KTL) Series
User Manual
No.
Parameter
6
Active islanding
7
Voltage rise
suppression
8
Voltage rise
suppression
reactive
adjustment point
9
Voltage rise
suppression active
derating point
10
Frequency change
Issue 02 (2017-07-30)
Description
voltage ride-through
(HVRT).
Specifies whether to
enable the active
islanding protection
function.
The standards of
certain countries and
regions require that
the active power of the
SUN2000 be derated
according to a certain
gradient when the
output voltage exceeds
a certain value.
The standards of
certain countries and
regions require that
the SUN2000 must
generate a certain
amount of reactive
power when the
output voltage exceeds
a certain value.
The standards of
certain countries and
regions require that
the active power of the
SUN2000 be derated
according to a certain
gradient when the
output voltage exceeds
a certain value.
The SUN2000 triggers
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Default
Value
N/A
N/A
%
The default
%
value varies
depending on
the grid code.
The displayed
value prevails.
N/A
The default
7 Man-Machine Interactions
Value Range
Remarks
Disable
N/A
Enable
Disable
N/A
Enable
[100, 115]
This
paramet
er is
displaye
d when
Voltage
rise
suppres
sion is
set to
[100, 115]
Enable.
The
value of
Voltage
rise
suppres
sion
active
deratin
g point
must be
greater
than
that of
Voltage
rise
suppres
sion
reactiv
e
adjust
ment
point.
Disable
N/A
88

Advertisement

Table of Contents
loading