No.
Parameter
Description
24
Maximum
Specifies the output
active
upper threshold for the
power
maximum active
power to adapt to
various market
requirements.
25
Tracking
Selects a controller
system
vendor.
controller
26
Duration
The standards of
for
certain countries and
determinin
regions require that
g
the SUN2000 should
short-time
not disconnect from
grid
the power grid if the
disconnecti
power grid
on
experiences a
short-time failure. The
SUN2000 needs to
restart quickly after
the power grid
recovers.
27
Adjust
Specifies the initial
total
energy yield of the
energy
SUN2000. This
yield
parameter is used in
SUN2000 replacement
scenarios. Set the
initial energy yield of
the new SUN2000 to
the total energy yield
of the old SUN2000 to
ensure continuous
statistics of
cumulative energy
yield.
28
DC input
If DC input detection
detection
is set to Disable, the
SUN2000 does not
perform automatic DC
input detection or
manual DC output
detection.
29
Commande
The standards of
d shutdown
certain countries and
hold after
regions require that
power
the SUN2000 remains
recovery
in the commanded
Issue 02 (2017-07-30)
Unit
Default
Value
kW
Pmax_limit
N/A
N/A
ms
3000
kWh
N/A
N/A
Enable
N/A
The default
value varies
depending
on the grid
code. The
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Value Range
Remarks
[0.1,
N/A
Pmax_limit]
N/A
N/A
[500, 20000]
N/A
[0.00,
N/A
42949600.00]
Disable
N/A
Enable
Disable
N/A
Enable