Troubleshooting - Huawei SUN2000-55KTL-HV-D1 User Manual

Sun2000-55ktl; sun2000-60ktl series
Hide thumbs Also See for SUN2000-55KTL-HV-D1:
Table of Contents

Advertisement

SUN2000-(55KTL, 60KTL) Series
User Manual
Item
Grounding
reliability

8.2 Troubleshooting

Alarm severities are defined as follows:
Table 8-2 Common alarms and troubleshooting measures
Alarm ID
Alarm
Name
103
High DC
Input
Voltage
Issue 02 (2017-07-30)
Check Method
Check that the idle COM, USB, and
AC OUTPUT ports are locked by
waterproof caps.
Check that ground cables are securely
connected.
Major: The inverter enters the shutdown mode and disconnects from the power grid to
stop generating electricity after a fault occurs.
Minor: Some components are faulty but the inverter can still generate electricity.
Warning: The inverter output power decreases due to external factors.
Alarm
Possible Cause
Severity
Major
Cause ID = 1
The PV array is not
properly configured.
Excessive PV modules are
connected in series to PV
strings 1 and 2, and
therefore the PV string
open-circuit voltage
exceeds the inverter
maximum MPP voltage.
Cause ID = 2
The PV array is not
properly configured.
Excessive PV modules are
connected in series to PV
strings 3 and 4, and
therefore the PV string
open-circuit voltage
exceeds the inverter
maximum MPP voltage.
Cause ID = 3
The PV array is not
properly configured.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
Maintenance Interval
months to a year.
The first inspection is
half a year after the
initial commissioning.
From then on, perform
the inspection once six
months to a year.
Suggestion
Cause ID = 1
Reduce the number of PV
modules connected in series to
PV strings 1 and 2 until the
open-circuit voltage is less than
or equal to the maximum inverter
input voltage. After the PV array
configuration is corrected, the
inverter alarm disappears.
Cause ID = 2
Reduce the number of PV
modules connected in series to
PV strings 3 and 4 until the
open-circuit voltage is less than
or equal to the maximum inverter
input voltage. After the PV array
configuration is corrected, the
inverter alarm disappears.
Cause ID = 3
Reduce the number of PV
modules connected in series to
PV strings 5 and 6 until the
open-circuit voltage is less than
93