SUN2000-(55KTL, 60KTL) Series
User Manual
Parameter List
No.
Parameter
1
LVRT
2
LVRT threshold
3
LVRT
undervoltage
protection shield
4
LVRT reactive
power
compensation
power factor
5
High voltage
ride-through
Issue 02 (2017-07-30)
Description
When the power grid
voltage is abnormally
low for a short time,
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called LVRT.
Specifies the threshold
for triggering LVRT.
Specifies whether to
shield the
undervoltage
protection function
during LVRT.
During LVRT, the
SUN2000 needs to
generate reactive
power to support the
power grid. This
parameter is used to
set the reactive power
generated by the
SUN2000.
When the power grid
voltage is abnormally
high for a short time,
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called high
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Default
Value
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
V
N/A
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
7 Man-Machine Interactions
Value Range
Remarks
Disable
N/A
Enable
[50%Vn,
N/A
92%Vn]
Disable
N/A
Enable
[0, 3]
For
example, if
you set
LVRT
reactive
power
compensat
ion power
factor to 2,
the reactive
power
generated
by the
SUN2000
is 20% of
the rated
power
when the
AC voltage
drops by
10% during
LVRT.
Disable
N/A
Enable
87