BACK UP AND RESTORE SETTINGS
Second, a message can display that the URS file is part of a device folder and to use the device's CID file. This means
that the URS file is from UR version 7.3 or higher, has the IEC 61850 software option in the order code, and is part of the
device folder. The user is trying to add a URS file from inside a device's folder. Instead, the user needs to use the CID file
from the device folder.
These messages display because the roles of the protection engineer and network engineer can be separate. The
former can require a URS file, while the latter can require stored Modbus settings and protection schemes.
4.
Manually copy the remaining settings, outlined as follows.
To restore settings from an IID file using EnerVista software:
1.
In Windows, make a copy the IID file with a cid extension.
2.
Connect to the device in the Online Window area.
3.
In the Offline Window area, right-click Devices and select Import Devices from SCD.
4.
Navigate to and select the file with .cid extension. When prompted, enter a file name to give to an intermediate URS
file. The URS file is added to the Offline Window area.
5.
Drag the imported file in the Offline Window to the device in the Online Window. Note that the
also is written to a device, and the accepting relay is put into "Programmed" or "Not Programmed" mode as
configured in the offline file.
6.
Manually copy the remaining settings, outlined as follows.
To restore settings from an IID using SFTP:
1.
In Windows, make a copy the IID file with a cid extension.
2.
On a computer on the same subnetwork as the UR device, open a SFTP client application, such as WinSCP. Note that
TFTP cannot be used here.
3.
Use the device's IP address as the host name.
4.
If the device has the CyberSentry option, use the User Name of "Administrator" or "Engineer", and the password
programmed for the selected role. The default password is "ChangeMe1#" (without quotation marks).
5.
If the device does not have the CyberSentry option, use the User Name of "Setting", and the password programmed for
the Setting role. The default password is "ChangeMe1#" (without quotation marks).
6.
Upload the backup file copy with the CID extension. WinSCP uses drag-and-drop or copy-and-paste for this.
7.
Manually copy the remaining settings, outlined as follows.
To manually copy remaining settings:
1.
Settings listed in section 4.1.2 Settings Files are not transferred to the UR device with settings files. Enter them
manually either via the front panel or via EnerVista UR Setup software. The values that these settings had at the time
10
the backup was created are contained within the backup file, accessed through EnerVista UR Setup software.
10-10
Figure 10-8: Importing an SCD or CID file
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 10: MAINTENANCE
value
RELAY SETTINGS