PRODUCT SETUP
SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME
5.3.4 Communications
5.3.4.1 Menu
SETTINGS PRODUCT SETUP COMMUNICATIONS
COMMUNICATIONS
5
5.3.4.2 Serial ports
The T60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is for local use and
is fixed at 19200 baud and no parity. The rear COM2 port is used for either RS485 or RRTD communications.
SETTINGS PRODUCT SETUP COMMUNICATIONS SERIAL PORTS
SERIAL PORTS
5-28
: "Self-reset"
: "0.20 s"
SERIAL PORTS
NETWORK
IPv4 ROUTE TABLE
MODBUS PROTOCOL
PROTOCOL
DNP PROTOCOL
DNP / IEC104
POINT LISTS
IEC 61850 PROTOCOL
WEB SERVER
HTTP PROTOCOL
TFTP PROTOCOL
IEC 60870-5-104
PROTOCOL
EGD PROTOCOL
IEC103
PROTOCOL
COM2 USAGE:
RS485
RRTD SLAVE ADDRESS:
254
RS485 COM2 BAUD
RATE: 19200
RRTD BAUD RATE:
19200
menu:
See below
See page 5-29
See page 5-34
See page 5-37
See page 5-38
See page 5-39
See page 5-42
Access in EnerVista
See page 5-43
See page 5-85
See page 5-86
See page 5-86
See page 5-88
See page 5-89
Range: RS485, RRTD
Range: 1 to 254 in steps of 1. Shown only if the COM2
USAGE setting is "RRTD."
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Shown only if
the COM2 USAGE is setting is "RS485."
Range: 1200, 2400, 4800, 9600, 19200. Shown only if
the COM2 USAGE is setting is "RRTD."
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS