GE T60 Instruction Manual page 148

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

FRONT PANEL INTERFACE
Status indicators
IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, the
relay has been programmed
4
TROUBLE — Indicates that the relay has detected an internal problem
TEST MODE — Indicates that the relay is in test mode. For more information, see the Test Mode section in the Settings
chapter.
TRIP — Indicates that the selected FlexLogic operand serving as a Trip switch has operated. This indicator always
latches; the reset command must be initiated to allow the latch to be reset.
ALARM — Indicates that the selected FlexLogic operand serving as an Alarm switch has operated. This indicator is
never latched.
PICKUP — Indicates that an element is picked up. This indicator is never latched.
Event-cause indicators
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
"Enabled" or "Latched." If a protection element target setting is "Enabled," then the corresponding event cause LEDs
remain on as long as operate the operand associated with the element remains asserted. If a protection element target
setting is "Latched," then the corresponding event cause LEDs turn on when the operate operand associated with the
element is asserted and remain on until the
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
VOLTAGE — Indicates voltage was involved
CURRENT — Indicates current was involved
FREQUENCY — Indicates frequency was involved
OTHER — Indicates a composite function was involved
PHASE A — Indicates phase A was involved
PHASE B — Indicates phase B was involved
PHASE C — Indicates phase C was involved
NEUTRAL/GROUND — Indicates that neutral or ground was involved
User-programmable indicators
The second and third panels provide 48 amber LED indicators whose operation is controlled by the user. Support for
applying a customized label beside every LED is provided.
4-22
Figure 4-24: LED panel 1
button on the front panel is pressed after the operand is reset.
RESET
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES