GE T60 Instruction Manual page 211

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that
is connected to these ports.
The RS485 port can be connected to a computer running EnerVista UR Setup. This software can download and upload
setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained
and connected to a distributed control system (DCS), power line carrier (PLC), or a computer using the RS485 ports.
The baud rate for standard RS485 communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800,
33600, 38400, 57600, or 115200 bps.
For the RS485 port, the minimum time before the port transmits after receiving data from a host can be set. This feature
allows operation with hosts that hold the RS485 transmitter active for some time after each transmission.
If the
setting is "RRTD," then the COM2 port is used to monitor the RTDs on a remote RTD unit. The remote RTD
COM2 USAGE
unit uses the Modbus RTU protocol over RS485. The RRTD device must have a unique address from 1 to 254. The baud rate
for RRTD communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, or 19200 bps.
If the RS485 COM2 port is used for an RRTD, then there must not be any other devices connected in the daisy-chain for any
other purpose. The port is strictly dedicated to RRTD usage when COM2 USAGE is selected as "RRTD."
For changes to the
COM2 USAGE
5.3.4.3 Ethernet network topology
The T60 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP
address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND
operation performed between their respective IP address and mask produces a different result. Communication becomes
unpredictable when more than one port is configured to the same subnet.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
Single LAN, no redundancy
The topology shown in the following figure allows communications to SCADA, local configuration/monitoring through
EnerVista, and access to the public network shared on the same LAN. No redundancy is provided.
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
RS485 COM2 PARITY:
None
RS485 COM2 RESPONSE
MIN TIME: 0 ms
setting to take effect, cycle power to the T60.
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
PRODUCT SETUP
5
5-29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents