GE T60 Instruction Manual page 362

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

FLEXLOGIC
specified operators to create an output. The final output of an equation is a numbered register called a virtual output.
Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of
parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, or flag set) or 0
(=OFF, or flag not set). Each equation is evaluated at least four times every power system cycle.
Some types of operands are present in the relay in multiple instances, for example contact and remote inputs. These types
of operands are grouped together (for presentation purposes only) on the faceplate display. The table lists characteristics
of the different types of operands.
Table 5-25: T60 FlexLogic operand types
Operand type
Contact Input
Contact Output
(type Form-A contact
only)
Direct Input
Element
5
(Analog)
Element
(Digital)
Element
(Digital Counter)
Fixed
RxGOOSE Boolean
Virtual Input
Virtual Output
The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.
5-180
State
Example of format
On
Cont Ip On
Off
Cont Ip Off
Contact Closed
Cont Op 1 Closed
Current On
Cont Op 1 Ion
Voltage On
Cont Op 1 VOn
Voltage Off
Cont Op 1 VOff
On
DIRECT INPUT 1 On
Pickup
PHASE TOC1 PKP
Dropout
PHASE TOC1 DPO
Operate
PHASE TOC1 OP
Block
PHASE TOC1 BLK
Pickup
Dig Element 1 PKP
Dropout
Dig Element 1 DPO
Operate
Dig Element 1 OP
Higher than
Counter 1 HI
Equal to
Counter 1 EQL
Lower than
Counter 1 LO
On
On
Off
Off
On
RxGOOSE Boolean 1 On
On
Virt Ip 1 On
On
Virt Op 1 On
Characteristics
[Input Is '1' (= ON) if...]
Voltage is applied presently to the input (external contact
closed)
Voltage is not applied presently to the input (external
contact open)
Contact output is closed
Current is flowing through the contact
Voltage exists across the contact
Voltage does not exist across the contact
The direct input is presently in the ON state
The tested parameter is presently above the pickup setting
of an element that responds to rising values or below the
pickup setting of an element that responds to falling values
This operand is the logical inverse of the above PKP
operand
The tested parameter has been above/below the pickup
setting of the element for the programmed delay time, or
has been at logic 1 and is now at logic 0 but the reset timer
has not finished timing
The output of the comparator is set to the block function
The input operand is at logic 1
This operand is the logical inverse of the above PKP
operand
The input operand has been at logic 1 for the programmed
pickup delay time, or has been at logic 1 for this period and
is now at logic 0 but the reset timer has not finished timing
The number of pulses counted is above the set number
The number of pulses counted is equal to the set number
The number of pulses counted is below the set number
Logic 1
Logic 0
The RxGOOSE Boolean is presently in the ON state
The virtual input is presently in the ON state
The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL