GROUPED ELEMENTS

5.7 Grouped elements
5.7.1 Overview
Each protection element can be assigned up to six sets of settings with designations 1 to 6. The performance of these
elements is defined by the active setting group at a given time. Multiple setting groups allow the user to conveniently
change protection settings for different operating situations (for example, altered power system configuration or season of
the year). The active setting group can be preset or selected in the
later in this chapter). See also the Introduction to Elements section at the beginning of this chapter.
5.7.2 Setting group 1
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)
 SETTING GROUP 1
5
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.7.3 Distance
5.7.3.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  DISTANCE
 DISTANCE
5-204
 DISTANCE
 POWER SWING
 DETECT
 LOAD ENCROACHMENT
 TRANSFORMER
 PHASE CURRENT
 NEUTRAL CURRENT
 GROUND CURRENT
 NEGATIVE SEQUENCE
 CURRENT
 BREAKER FAILURE
 VOLTAGE ELEMENTS
 POWER
DISTANCE
SOURCE: SRC 1
menu (see the Control Elements section
SETTING GROUPS
See below
See page 5-225
See page 5-234
See page 5-235
See page 5-244
See page 5-256
See page 5-264
See page 5-271
See page 5-277
See page 5-287
See page 5-298
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6