CHAPTER 6: ACTUAL VALUES
This menu displays metered values for current and power demand. The "SRC 1" text is replaced by the name programmed
by the user for the associated source (see
The relay measures (absolute values only) the source demand on each phase and average three phase demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier demand penalties or for statistical
metering purposes. Demand calculations are based on the measurement type selected in the
menu. For each quantity, the relay displays the demand over the most recent demand time interval, the
 DEMAND
maximum demand since the last maximum demand reset, and the time and date stamp of this maximum demand value.
Maximum demand quantities can be reset to zero with the
6.4.3.9 Frequency metering
ACTUAL VALUES  METERING  SOURCE SRC 1  FREQUENCY
 FREQUENCY
 SRC 1
The metered frequency values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by the
user for the associated source (see
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
SRC 1 DMD IA DATE:
2001/07/31 16:30:07
SRC 1 DMD IB:
0.000 A
SRC 1 DMD IB MAX:
0.000 A
SRC 1 DMD IB DATE:
2001/07/31 16:30:07
SRC 1 DMD IC:
0.000 A
SRC 1 DMD IC MAX:
0.000 A
SRC 1 DMD IC DATE:
2001/07/31 16:30:07
SRC 1 DMD W:
0.000 W
SRC 1 DMD W MAX:
0.000 W
SRC 1 DMD W DATE:
2001/07/31 16:30:07
SRC 1 DMD VAR:
0.000 var
SRC 1 DMD VAR MAX:
0.000 var
SRC 1 DMD VAR DATE:
2001/07/31 16:30:07
SRC 1 DMD VA:
0.000 VA
SRC 1 DMD VA MAX:
0.000 VA
SRC 1 DMD VA DATE:
2001/07/31 16:30:07
SETTINGS  SYSTEM SETUP  SIGNAL SOURCES
CLEAR RECORDS  CLEAR DEMAND RECORDS
SRC 1 FREQUENCY:
0.00 Hz
SETTINGS  SYSTEM SETUP  SIGNAL SOURCES
METERING
).
SETTINGS  PRODUCT SETUP
command.
).
6
6-21