Connection Of The Cc-Link Dedicated Cables - Toshiba AJ65VBTCU-68ADVN User Manual

A melsec programmable controller, analog-digital converter module
Table of Contents

Advertisement

4 SETUP AND PREPARATION BEFORE OPERATION

4.8.2 Connection of the CC-Link dedicated cables

[CC-Link dedicated cable wiring diagram]
Master station
Terminating
resistor
DA
(Blue)
DB
(White)
DG
(Yellow)
SLD
FG
Ver.1.10 Compatible CC-Link dedicated cable (FANC-110SBH, CS-110, FA-CBL200PSBH)
4 - 12
Connect the CC-Link dedicated cable between the AJ65VBTCU-68ADVN/ADIN and
master module as shown below.
DC24V
[Power supply/FG cable wiring diagram]
External supply
power cable (IN)
External supply
power cable (OUT)
The power cables cannot be conected with the
other remote I/O module having the one-touch
connector for power supply.
Online connector
for communication
NC
NC
NC
NC
NC
One-touch connector plug
for communication
(A6CON-L5P)
Online connector for power supply/FG (A6CON-PWJ5P)
Online connector
for power supply/FG
1
2
3
4
5
1
2
3
4
5
CONA
1
1
DA
2
2
DB
3
3
DG
4
4
NC
5
5
SLD
CONB
1
1
DA
2
2
DB
3
3
DG
4
4
NC
5
5
SLD
MELSEC-A
Online connector for communication
(A6CON-LJ5P)
One-touch connector plug
with terminating resistor
A6CON-TR11
Always fit a non-wired
connector to the open
connector for power
supply/FG.
One-touch connector plug for power supply/FG
(A6CON-PW5P/A6CON-PW5P-SOD)
CONC
1
FG
+24V (UNIT)
2
24G (UNIT)
3
AG
4
FG1
5
COND
1
FG
2
+24V (UNIT)
24G (UNIT)
3
4
AG
5
FG1
Online connector
for communication
1
2
3
4
5
1
2
3
4
5
Terminating
resistor
(A6CON-TR11)
CONA
1
DA
2
DB
3
DG
4
NC
5
SLD
CONB
1
DA
2
DB
3
DG
4
NC
5
SLD
4 - 12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj65vbtcu-68adin

Table of Contents