Ethernet - Balluff BNI EIP-502-105-Z015 User Manual

Ip67 modules 4 io link/in-/outputs,12 in-/outputs
Hide thumbs Also See for BNI EIP-502-105-Z015:
Table of Contents

Advertisement

4
Technical data

4.5. Ethernet

4.6. Function
indicators
Modul status
Port
www.balluff.com
Ethernet IP port
Connection for Ethernet IP port
Cable types per IEEE 802.3
Data transmission rate
Max. cable length
Flow control
LED
Display
green
UA
red
green
US
red
green flashing
green
Mod
red flashing
red-green flashing
off
green flashing
Net
green
red flashing
red-green flashing
off
100
yellow
LNK
green
Each Port has two two-colour LEDs to indidcate the I/O-States.
Display
Status
off
I/O-State
yellow
I/O-State
red
Short-circuit
green
IO Link
Green
IO Link
flashing
red
Short-circuit
red
IO Link
flashing
1 x 10Base-/100Base-Tx
M12, D-coded
Shielded twisted pair min. STP CAT 5/ STP CAT 5e
10/100 Mbit/s
100 m
Half Duplex/Full Duplex (IEEE 802.33x-Pause)
Status –LEDs: Modul status
Port/Pin LEDs:
Status of the IO Link and I/O ports
Description
Output power OK
Low Output power (< 18V)
Input power OK
Low Input power (<18V)
Wrong or no configuration on module
Modul operating
Fixed busclock is not possible
Initial sequence
Module got no IP address
Module got IP, but no connection could be established
Connection established
Connection timeout
Initial sequence
Bus clock: 10 Mbit/s
Bus clock: 100 Mbit/s
Data transfer
Description
State of the Input or Output Pin is 0
State of the Input or Output Pin is 1
single LED:
Short-circuit on dedicated Pin (only if
this pin is used as an output)
both LEDs:
Short-circuit between Pin 1 and 3 or
Short-circuit on both output pins
IO Link communication running
No IO Link communication
single LED:
Short-circuit on Pin 4
both LEDs:
Short-circuit between Pin 1 and 3
IO Link Device has wrong configuration
9

Hide quick links:

Advertisement

Table of Contents
loading