D. Gas Connection - Heat & Glo SLR-X-AU Installation Manual

Hide thumbs Also See for SLR-X-AU:
Table of Contents

Advertisement

D. Gas Connection

• Refer to Reference Section 3 for location of gas line
access in appliance.
• Gas line may be run through knockout(s) provided.
• The gap between supply piping and gas access hole
may be caulked with caulk with a minimum of 300 ºF
(149 ºC) continuous exposure rating or stuffed with
non-combustible, unfaced insulation to prevent cold air
infiltration.
• Ensure that gas line does not come in contact with outer
wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm)
connection on manual shutoff valve.
WARNING! Risk of Fire or Explosion! Support control
when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire or Explosion! Gas build-up
during line purge could ignite.
• Purge should be performed by qualified service
technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks or
open flames.
Light the appliance. It will take a short time for air to purge
from lines. When purging is complete the appliance will
light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fittings and connections with a non-corrosive
commercially available leak-check solution. DO NOT use
open flame. Fittings and connections could have loos-
ened during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings.
This valve has been preset at the factory.
E. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 ft. (610 m) elevation:
Reduce input rate 4% for each 1000 ft. (305 m) above
2000 ft. (610 m).
42
Heat & Glo • SLR-X-AU Installation Manual • 2493-980 Rev. B • 12/17
F. Air Shutter Setting
The Natural Gas Shutter setting is pre-set for the mini-
mum (vertical and horizontal) one elbow horizontally ter-
minating application. For appliances intended to operate
with Propane or Butane Gas, a conversion kit is required
and the air shutter is to be adjusted during the conversion
and shutter verification process.
Air shutter settings should be adjusted by a qualified
service technician at the time of installation. Adjust air
shutter for longer vertical runs. See Figure 9.4.
• Loosen the 1/4 in. (6 mm) screw.
• Twist the air shutter to adjust.
• Tighten the 1/4 in. (6 mm) screw.
Shutter Setting Verification / Flame Appearance
• After 15 minutes, the flames will be a yellow/blue mix.
The front flames may be blue at this time.
• After 30 minutes, the flames should be yellow with
some blue flames near the burner ports.
• After 1 hour, the flame will be at is maximum maturity.
NOTICE: If flames lack the desired yellow appearance,
adjust the shutter to a more "closed" position. If flames
are dark orange with smoky tips, adjust the shutter to a
more "open" position.
Figure 9.4 Air Shutter Location
Air Shutter Settings
Glass Media Option
or Driftwood Option
SLR-X-AU (NG)
1/8 in. (3 mm)
SLR-X-AU (LP)
Full Open
SLR-X-AU (B)
Full Open
Traditional
Log Option
1/2 in. (13 mm)
3/8 in. (10 mm)
5/8 in. (16 mm)

Advertisement

Table of Contents
loading

Table of Contents