Troubleshooting - Procom EL250RYLB-O Owner's Operation And Installation Manual

Compact vent-free fireplace system
Table of Contents

Advertisement

WARNING:Make sure that power is
turn off before proceeding....
OBSERVED PROBLEM
No spark when press in ignition button
When pressing the button of ignitor but-
ton is pressed, there is spark at ODS/
pilot but no ignition
ODS/pilot lights but flame is continuous
igniting and the main burner couldn't be
lit.
Burner does not light after ODS/pilot is
lit

TROUBLESHOOTING

WARNING: Turn off and let cool
before servicing. Only a qualified ser-
vice person should service and repair
fireplace.
POSSIBLE CAUSE
1. No power to heater
2. No battery in transmitter or battery isn't
correctly assembly
1. Gas supply turned off or equipment
shut off valve closed
2. Air in gas lines when installed.
3. Depleted gas supply
4. ODS/pilot is clogged
5. Gas regulator setting is not correct
6. Pilot electrude position is not correct
7. Wire is not correct or loosen
8 Gas valve is damage
1. Thermocouple connection loose
at control board
2.
Pilot flame not touching thermcouple
which allows thermocouple to cool,
causing pilot flame to go out. This
problem could be caused by one or
both of the following
A) Low gas pressure
B) Dirty or partially clogged ODS/
pilot
3. Thermocouple damaged
4. Control valve damaged
1. Burner orifice clogged
2. Inlet gas pressure is too low
3. Burner orifice diameter is too small
4. Thermocouple leads disconnected
or improperly connected
5. Burners will not come in remote
position
1 4
CAUTION: Never use a wire,
needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.
REMEDY
1. Check the electric power
2. Place or replace the battery.
1.
Turn on gas
supply
equipment shutoff valve
Press ON/OFF button again
2.
until air
is removed .
3. Contact
local
propane/LP
company
4
Clean
ODS/pilot (see Cleaning and
Maintenance,page 12 ) or replace
ODS/pilot assembly
Replace gas control
5.
6. Replace Pilot
7. Check the wine and make wine correct.
8. Replace gas valve
1 .
H a n d t i g h t e n t h e c o n n e c t o r s .
2. A) Contact local propane/LP gas
company.
B) Clean ODS/pilot (see Cleaning
and Maintenance, page 12) or replace
ODS/pilot assembly
3.
Replace thermocouple
4.
Replace control valve
1 . C l e a n b u r n e r ( s e e C l e a n i n g
and Maintenance, page 12) or replace
burner orifice.
2. Contact
local
propane/LP
company
3. Replace burner orifice
4. Reconnect leads (see wiring diagram)
5. Replace battery in transmitter and
receiver
or
open
gas
gas