Diagnosis Telegram In Professional Mode - Pepperl+Fuchs VAG-PB-KF-R4 Manual

As-interface/profibus gateway p20
Table of Contents

Advertisement

8.4.2 Diagnosis telegram in professional mode

The diagnosis telegram contains 24 bytes in the professional mode. The structure is
represented in the following table.
byte
content
0
station status 1
1
station status 2
2
station status 3
3
station number DP-master
4-5
manufacturer code
6
length of the device-based diagnosis (19
7
execution control flags
8-11
configuration error list
12-15
LCS (List of Corrupted Slaves)
16
execution control flags
17-20
configuration error list
21-24
LCS (List of Corrupted Slaves)
execution control flags see appendix, chapter 11.2.
The configuration error list is built up as the LPS (see appendix, chapter 11.1). A bit
in the configuration error list is set, if the concerning bit in the LPS (List of Projected
Slaves) differs from the one in the LDS (List of Detected Slaves) or if the projected
AS-i configuration data (I/O- and ID-code) of the concerning AS-i slave differ from the
detected configuration in the AS-i circuit.
The LCS is explained in chapter 7 (advanced AS-i diagnostics).
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
AS-i/PROFIBUS Gateway
Profibus-DP
=13
)
dez
hex
AS-i Master 1
AS-i Master 2
Copyright Pepperl+Fuchs, Printed in Germany