Standard Mode; Remote Io Points - Pepperl+Fuchs CC-LINK Series Compact Manual

Table of Contents

Advertisement

CC-Link Gateways
Data transmission modes of the CC-Link Gateways
6.1

Standard mode

The Standard Mode has the following features:
the gateway occupies 3 stations and has a double cycle setting.
The last 2 words are reserved for "Message Transmission".
The AS-i process data is mapped into the Buffer Memory Area (BFM).
All acyclic requests are handled by "Message Transmission" using cyclic
data.
6.1.1

Remote IO Points

Remote to Host
Address
RXm
RXm+1
RXm+2
...
RXm+9
EC-Flags and Fault Detector
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
15 14 13 12 11 10 9
AS-i circuit 1: EC-Flags and Fault Detector
Short Cut
Cfg. OK
S0
Aaasn
Aaavail
CM
NA
APF
AS-i Power Fail (AS-i voltage below 19 V)
Offl
NPF
reserved
PWRw
Power Warning (AS-i voltage below 22.5 V)
reserved
EF
OV
Noise
reserved
8
7
6
5
4
3
reserved
reserved
Name
Configuration OK
Slave Address 0 detected
Auto Address Assign
Auto Address Available
Configuration Mode active
Normal Operation active
Off-line
No Peripheral Fault
reserved
reserved
Earth Fault
Over-voltage on AS-i
Noise
reserved
2
1
0
Tab. 6-2.
Tab. 6-3.
11