3 Operation and visualization

3.5 Event list

Events
Event
definition
Text
assignment
Freely definable
texts
Standard texts
36
Various events can initiate texts which are included in the event list and saved
in the internal memory or on diskette. Events may include:
- alarms triggered by out-of-limit conditions on individual channels,
- external texts triggered through logic inputs,
- system messages (e. g. power ON/OFF, summer/winter time changeover),
Foll all events, except for system messages, it is possible to configure whether
- the message text is to be included in the event list,
- the standard text internal to the instrument
- or one of the texts (see below) is used.
The texts (standard texts or 18 freely definable texts) are assigned to the
events at the operating level "Configuration"
(v Chapter 4 "Configuration parameters").
18 texts can be freely defined, up to a length of 20 characters.
The instrument offers standard texts as listed in the following table:
Standard text
Chanx low alarm ON
Chanx low alarm OFF
Chanx high alarm ON
Chanx high alarm OFF
Alarm counter/int. x ON
Alarm counter/int. x OFF
Logic input y ON
Logic input y OFF
Logic channel y ON
Logic channel y OFF
Counter x: y
Power ON
Power OFF
Data lost
Summer time start
Summer time end
New configuration
Counter/int. x from y reset to z
„Text 1 — 18"
Note
x = channel number
y = input number
x = counter channel number
y = counter value (9 digits)
x = counter/int. channel number
y = old counter/int. value (9 digits)
z = new counter/int. value (9 digits)
18 freely definable texts