Interval Type
<int_type>0</int_type>
Interval type is a single digit value. Only 0 or 1 is
valid:
1 – Checkback Hours of the day
0 – Periodic checkback select
Hours Of The Day
(Valid only when 'Hours of the Day' is selected)
<time1>5</time1>
<time2>10</time2>
<time3>15</time3>
<time4>20</time4>
Hours of the day 0 – 23 in a 24 hour clock format.
This indicates the hours of the day checkback needs
to run.
Periodic Checkback
(Valid only when 'Checkback Hours' is selected)
<test_period>8</test_period>
Periodic Checkback is 0 – 99. This indicates the
number of hours to wait before the next Checkback
test will run.
Carrier Recovery
<reco_enab>0</reco_enab>
Carrier Recovery is a single digit value. Only 0 or 1
is valid:
1 – Enable Carrier Recovery
0 – Disable Carrier Recovery
Recovery Window
<recovery_time>10</recovery_time>
Recovery Window is a number between the range
of 0 – 24 hours. It specifies how long a UPLC™
will be in Recovery Mode before indicating a
Delayed Alarm.
Recovery Period
<reco_time>30</reco_time>
May 2012
Chapter 5. Installation/Configuration Procedures
Recovery Period number between the range of 5 –
60 minutes. It specifies the time between Master
initiated Checkback tests when the UPLC™ is in
Recovery Mode.
Loopback Duration
<loop_time>10</loop_time>
Loopback Duration is 4 – 60 seconds. It specifies
how long a UPLC™ will key its transmitter at high
and low power during a Loopback test.
Synchronize Clock Automatically
<sync_enab>1</sync_enab>
Synchronize Clock Automatically is a single digit
value. Only 0 or 1 is valid:
1 – Enable Automatic Synchronization
0 – Disable Automatic Synchronization
5
Page 5–7