UPLC™ Application Manual
Unblock Delay is a number between the range of 0
– 100 ms.
Fade Drop Delay (Valid for AM Mode Only)
<fade_drop_delay>0</fade_drop_delay>
Fade Drop Delay is 0 – 15 ms in 1 ms steps
Trip Test (Valid for FSK Mode Only)
<ttu0>1</ttu0>
Trip Test is a single digit value. Only 1 or 2 is valid:
1 – Disabled
2 – Enabled
Voice
<voice>2</voice>
Voice is a single digit value. Only 1 or 2 is valid:
1 – Beep Disabled
2 – Beep Enabled
Guard Before Trip (Valid for FSK Mode Only)
<guard_t0>2</guard_t0>
Guard Before Trip is a single digit value between 1
& 3:
1 – Not Required
2 – Required
3 – Required But With Override
Blocking Priority (Valid for AM Mode Only)
<blk_pri0>1</blk_pri0>
Blocking Priority is a single digit value:
1 – Stop
2 – Start
Checkback (Valid for AM Mode Only)
<checkback0>0</checkback0>
Checkback is a single digit value. Only 0 or 1 is
valid:
0 – Checkback Disabled
1 – Checkback Enabled

Input/Outputs

Inputs
Contact Bounce
Page 5–4
<in1_hold>1</in1_hold>
Contact Bounce is between 0 to 15. Each unit
denotes 0.5 ms. As an example, 8 would be equal to
4ms.
Selection
<in1_selection>1</in1_selection>
Selection is a number between 0 & 8 or 9 depend-
ing on the mode:
FSK
0 – Not Used
1 – UB Key
2 – Power Off
3 – Trip Test
4 – 52B
5 – SOE Event 1
6 – SOE Event 2
7 – SOE Event 3
AM
0 – Not Used
1 – Carrier Start
2 – Carrier Stop
3 – Low Level Key
4 – Checkback Reset
5 – Checkback Initiate
6 – SOE Event 1
7 – SOE Event 2
8 – SOE Event 3
9 – Loopback Test
Active State
<in1_active_state>0</in1_active_state>
Active State is a single digit value. Only 0 or 1 is
valid:
0 – Application of Voltage
1 – Removal of Voltage
Trip Duty Outputs
Selection
<em1_selection>1</em1_selection>