Protective Relay Applications Using Frequency Shift Carriers; Directional Comparison Unblocking - Ametek UPLC CU44-VER04 Applications Manual

Universal power-line carrier
Table of Contents

Advertisement

3.1
Protective Relay
Applications Using
Frequency Shift Carriers
The UPLC™ carrier set is particularly suitable for
the following types of protective relay systems:

• Directional Comparison Unblocking

• Permissive Overreaching Transfer Trip
(POTT)
• Permissive Underreaching Transfer Trip
(PUTT)
• Dual Phase Comparison Unblocking
• Segregated Phase Comparison Unblocking
• Direct Transfer Trip
3.1.1
Directional Comparison
Unblocking
The Directional Comparison Unblocking systems
transmit a continuous blocking signal, except dur-
ing internal faults. The channel is generally a fre-
quency-shift keyed (FSK) power-line carrier. For
an internal fault, the FSK transmitter is shifted to
the "unblock" frequency. The transmitted power
in many applications is normally 1 W, boosted to
10 W during unblock operation.
The frequency-shift channel is monitored continu-
ously to prevent tripping when a loss of channel
occurs. The carrier receiver logic is shown in
Figure 3–1. Under normal conditions, a block fre-
quency is transmitted and OR-1 has no input.
Because AND-1 and AND-2 are not satisfied, OR-
Block
OR
Frequency
1
Unblock (Trip)
Frequency
Figure 3–1. Simplified Unblock Receiver Logic.
Chapter 3. Applications
Lockout
0-500
AND
AND
ms
1
2
0
(0=disabled)
Copyright © AMETEK
2 is not energized. For an internal fault, the block
frequency is removed. Assuming that the unblock
signal is shorted out by the fault, OR-1 provides a
direct input to AND-2 to satisfy its input require-
ments for 150 ms. AND-2 inputs to OR-2 to oper-
ate the RR or to provide input to the AND shown
in Figure 3–1. Without an unblock signal, 150 ms
is allowed for tripping. After this period, lock out
is initiated as one of the inputs to AND-2 is
removed. This resets the RR or removes the input
to AND. If the unblock signal is received, it inputs
directly to OR-2 to energize the RR or to provide
input to AND. The unblock signal also removes an
input to AND-1 to stop the timer. A channel fail-
ure (no block or unblock signal) provides input to
AND-1 and, after 150ms, locks out the relaying
and triggers an alarm. The operation of the scheme
shown in Figure 3–4 is given in Table 3–1 for
external and internal faults. The phase and ground
trip fault detectors at both stations must operate
for all internal faults; that is, they must overreach
the remote bus.
The dependability and security of Directional
Comparison Unblocking systems make them the
most attractive of the protective schemes for trans-
mission lines using power-line carrier channels.
Over-tripping is avoided by continuous blocking
and continuous channel monitoring. Only an
external fault within a certain time delay after
channel failure can result in over-tripping. This
time is selectable from 0-500ms.
The scheme is most
appropriate for two-ter-
minal lines, but is appli-
cable to multi-terminal
lines. Separate channels
OR
are required between each
To RR or
2
AND
terminal and the remote
terminal(s). A sample
schematic is shown in
Figure 3–2.