Uplc Dnp Attributes Page - Ametek UPLC CU44-VER04 Applications Manual

Universal power-line carrier
Table of Contents

Advertisement

UPLC™ Application Manual
8.1.1.2 Secondary DNP Web Page Settings
(Setting Up Data Points)
The UPLC™ sends only Binary Inputs and Analog
Inputs to an RTU or SCADA master station. There
are no DNP Outputs accepted by the UPLC™ from
an RTU or SCADA master station. All points are
programmable as to whether they will be included
in a particular class poll and also to what variation
(type of value) will be returned in the poll. All
points can be set to a Class of "off" if the point is
not valid for the selected UPLC™ function. All
binary points in the UPLC™ report a value of 0
when "off" and a value of 1 when "on".
A separate pop-up window/page appears when you
click on each of the 4 buttons at the bottom of the
main DNP page. Only one pop-up page can be dis-
played at a time. Pop-up pages should be closed
after viewing or changing. To close the page, you
must either click "Submit", to send the changes to
the UPLC™, or click the "X" in the upper right cor-
ner of the page if there are no changes.
Basic information regarding the UPLC™ is located
on the Attributes page. The following attributes, in
green cells, can be edited.
• User-Assigned Location Name
• User-Assigned ID Code Number
• User-Assigned Name for Outstation
Page 8–2
For the 3 DNP Input Web pages,
1) "UPLC Inputs" (Binary)
2) "UPLC Outputs" (Binary)
3) "UPLC Analog" (Analog)
the following settings must be made in the pop-up
Web pages.
• Event/Static Data Class = Off, 0–3
• Description = Long Character String that
• Default Variation for Static Data = 1–3 (1-5
• Default Variation for Event Data = 1–3 (1-5
Please refer to the following figures.
You Can Double Click in Green Cells to Edit.
Figure 8–2 UPLC DNP Attributes Page
(Admin > Protocol > DNP > Attributes)
User Can Enter Describing the DNP Input
for Analog Inputs only)
for Analog Inputs only)
N O T E