Point Name
0
3F DTT Trip Key
1
LR Trip Key
2
TX Power Off Key All FSK Modes TX RF Power Off Input Keyed (Turns TX Off for Test)
3
TX Pwr Boost Key All FSK Modes Power Boost Input has been Keyed
4
User SOE 1 Key
5
User SOE 2 Key
6
User SOE 3 Key
7
PC Key
8
Trip A Key
9
Trip B Key
10
Initiate Trip Test
11
2F DTT/POTT
Trip Key
12
TX Keyed Off
8.3 DNP Binary Inputs (UPLC
Outputs)
The UPLC™ has 10 or 14 binary outputs, depend-
ing on the model. Like UPLC™ inputs, you can
assign these outputs in numerous ways. The follow-
ing tables include all possible output selections for
the UPLC™ ON-OFF and FSK modes. Since there
are more selections than outputs, at any given time
some of these selections will be unassigned and
their on-line bits will be set to zero.
Page 8–4
Table 8–2 UPLC Inputs – DNP Points for FSK Mode
Setting Mode
Definition
3-Freq. Only
DTT Trip Input Keyed (for 3–Freq. Mode)
2 or 3-Freq.
Line Relaying Trip Input Keyed (Unblock/2F, UB/POTT/3F)
All FSK Modes SOE Event 1 Input has been Keyed
All FSK Modes SOE Event 2 Input has been Keyed
All FSK Modes SOE Event 3 Input has been Keyed
Phase Comp.
Phase Comparison Input has been Keyed
4-Freq. Only
Trip Channel A Input has been Keyed
4-Freq. Only
Trip Channel B Input has been Keyed
Testing Only
Trip Test Input has been Keyed
Option Enabled (for Testing Purposes Only)
2-Freq. Only
DTT Trip of POTT Trip Input has been Keyed
All FSK Modes Transmit Keyed Off