Ametek UPLC CU44-VER04 Applications Manual page 83

Universal power-line carrier
Table of Contents

Advertisement

Trip Duty Outputs is a single digit value between 0
& 2
FSK
0 – Not Used
1 – Guard
2 – Trip
AM
0 – Not Used
1 – Blocking Output
2 – Fade Alarm
Low Level Outputs
Selection
<prog1_selection>1</prog1_selection>
Low Level Outputs is a single or double-digit value
between 0 & 11 or 16 depending on the mode:
FSK
Phase Comparison
0 – Not used
1 – Trip Negative
2 – Trip positive
3 – Reflected Power
4 – Main RF Output
5 – Redundant RF Output
6 – Good Channel
7 – Noise
8 – Fade Alarm
9 – TX Shift High
10 – TX Shift Low
11 – General Failure
2F-Unblocking & 2F-POTT/DTT
0 – Not used
1 – Guard
2 – Trip
3 – Reflected Power
4 – Main RF Output
5 – Redundant RF Output
6 – Good Channel
May 2012
Chapter 5. Installation/Configuration Procedures
7 – Noise
8 – Fade Alarm
9 – TX Shift High
10 – TX Shift Low
11 – Checkback Trip
12 – General Failure
3-Frequency
0 – Not used
1 – LR Guard
2 – LR Trip
3 – Reflected Power
4 – Main RF Output
5 – Redundant RF Output
6 – Good Channel
7 – Noise
8 – Fade Alarm
9 – TX Shift High
10 – TX Shift Low
11 – LR Checkback Trip
12 DTT Guard
13 DTT Trip
14 DTT Checkback Trip
15 – General Failure
4-Frequency
0 – Not used
1 – A Guard
2 – A Trip
3 – Reflected Power
4 – Main RF Output
5 – Redundant RF Output
6 – Good Channel
7 – Noise
8 – Fade Alarm
9 – TX Shift to A
10 – TX Shift to B
11 – A Checkback Trip
12 B Guard
5
Page 5–5