Chapter 1. Ordering Information

Ordering Information

The UPLC™ carrier is functionally compatible with earlier type carrier equipment (e.g., KR, TC, TC-10,
TC-10A & TC-10B, TCF, TCF-10, TCF-10B). That is, you may use the UPLC™ with these other carrier
types at the opposite end of the line.
You may use the UPLC™ carrier set with the following types of relay systems:
• All Directional-Comparison Systems
• Phase-Comparison Systems
• Direct Transfer Trip Systems
Options include:
• Automatic Checkback Testing Facilities for periodic testing of the carrier channel at programmable
intervals (in ON-OFF mode)
• Trip Test Facility (in FSK mode)
The equipment identification number (catalog number) is displayed when you press "set" & is shown on
all of the webpages. The UPLC™ catalog number comprises eleven (11) characters, each in a specific
position. This number identifies the unit's technical characteristics and capabilities, as well as any option-
al modules installed in the unit.
The table on the following page provides a complete listing of the options for ordering a UPLC™, as well
as a sample catalog number. To order one or more UPLC™ units, simply identify the features you want
for each chassis. For example, — U S 1 N S C 1 A N S X — describes a UPLC™ with the fol-
lowing features:
Chassis: UPLC™
Configuration: Single Transceiver Unit
DC/DC Converter Power Supply: 110/125/250 Vdc
Redundant DC/DC Converter Power Supply: None
Outputs / Logic: Standard Outputs (7 Solid State & 3 Contacts) / No Special Logic
Ethernet Ports: 10/100 Base T / Redundant 10/100 Base T (with RJ-45 Connector)
Protocols / PC Interface (Front Port): No Protocol / RS-232 Front Port
Testing Facilities: Single Transceiver
Power Amp Features: Standard Power Amp
Backplate Option: Standard
Copyright © AMETEK