UPLC™ Application Manual
13 B Trip
14 B Checkback Trip
15 – General Failure
AM
0 – Not used
1 – Blocking Output
2 – Fade Alarm
3 – Reverse Power
4 – Main RF Output
5 – Redundant RF Output
6 – CB Off
7 – CB Passed
8 – Carrier Received
9 – CB Major Alarm
10 – CB Minor Alarm
11 – CB Delayed Alarm
12 – CB Carrier Recovered
13 – CB In Recovery Mode
14 – CB Test In Progress
15 – CB Auto Test Disabled
16 – General Alarm
NOTE: General Alarm is a valid option only for the
EM Outputs.
De-Energized State
<em1_selection>1</em1_selection>
De-energized State is a single digit value:
0 – Normally Open
1 – Normally Closed
Page 5–6

Checkback Configuration

Module Address
<address>0</address>
Module Address is a number between 0 and 10. 0
being the Master and 1-10 are Remote Modules
Primary Communication Mode
<prim_comm>1</prim_comm>
Primary Communication mode is a single digit
value. Only 0 or 1 is valid:
1 – Coded Communication Mode
0 – Timed Communication Mode
Auto Tests
<auto_test>1</auto_test>
Auto tests is a single digit value. Only 0 or 1 is
valid:
1 – Auto Tests On
0 – Auto Tests Off
Fallback Communication Mode
<fallback>0</fallback>
Fallback Communication Mode is a single digit
value. Only 0 or 1 is valid:
1 – Enable Fall back Communication
0 – Disable Fall back Communication
Low Power Tests
<low_pwr>0</low_pwr>
Low Power Tests is a single digit value. Only 0 or 1
is valid:
1 – Enable Low Power Tests
0 – Disable Low Power Tests
Last Module
<last_rem>1</last_rem>
Last Module is between 1 and 10; up to ten Remote
Modules can be assigned.
Retries
<retries>4</retries>
Retries is 0 – 15, indicating, up to 15 retries are
allowed.