No.2 process handgun electric motor version
Hide thumbs Also See for 19372:
Table of Contents

Advertisement

AREA
Tells where hazards
may occur.
Spray Area
General Use and
Maintenance
AH-13-01.3
HAZARD
Tells what the hazard is.
Explosion Hazard
Improper or inadequate oper-
ation and maintenance proce-
dures will cause a fire hazard.
Protection against inadvertent
arcing that is capable of caus-
ing fire or explosion is lost if
any safety interlocks are dis-
abled during operation.
Frequent Power Supply or
Controller shutdown indicates
a problem in the system requir-
ing correction.
Improper operation or mainte-
nance may create a hazard.
Personnel must be properly
trained in the use of this equip-
ment.
No. 2 Process Electric Motor Version - SAFETY
SAFEGUARDS
Tells how to avoid the hazard.
Electrostatic arcing must be prevented. Safe
sparking distance must be maintained be-
tween the parts being coated and the appli-
cator. A distance of 1 inch for every 10KV of
output voltage is required at all times.
Unless specifically approved for use in hazard-
ous locations, all electrical equipment must be
located outside Class I or II, Division 1 or 2
hazardous areas, in accordance with NFPA-
33.
Test only in areas free of flammable or com-
bustible materials.
The current overload sensitivity (if equipped)
MUST be set as described in the correspond-
ing section of the equipment manual. Protec-
tion against inadvertent arcing that is ca-
pable of causing fire or explosion is lost if the
current overload sensitivity is not properly
set. Frequent power supply shutdown indi-
cates a problem in the system which requires
correction.
Always turn the control panel power off prior to
flushing, cleaning, or working on spray system
equipment.
Before turning high voltage on, make sure no
objects are within the safe sparking distance.
Ensure that the control panel is interlocked
with the ventilation system and conveyor in ac-
cordance with NFPA-33, EN 50176.
Have fire extinguishing equipment readily
available and tested periodically.
Personnel must be given training in accodance
with the requirements of NFPA-33, EN 50-176.
Instructions and safety precautions must be read
and understood prior to using this equipment.
Comply with appropriate local, state, and national
codes governing ventilation, fire protection, oper-
ation maintenance, and housekeeping.