5.8 INPUTS AND OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel,
or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the
FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand
RESET OP
RESET OP (PUSHBUTTON)
shown above selects the operand that will create the

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE ANALOG
 INPUT 1
5
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the
ANALOG 1 DEFAULT MODE
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE analog input is defined by the
GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user to
configure GOOSE Analog, so that it can be used in a FlexElement.
GOOSE Analogs that represent current, voltage, power, frequency, angles, or power factor can be used in a FlexEle-
ment. The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz,
deg, and no text (blank setting) for power factor.
GOOSE Analogs can be compared to other GOOSE Analogs with any character string or no string.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other L30 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and
a PU base of 0.001 is 1.
5-218

RESETTING
RESET OPERAND:
Off
,
or
RESET OP (COMMS)
RESET OP (OPERAND)

IEC 61850 GOOSE ANALOGS
ANALOG
1 DEFAULT:
1000.000
ANALOG
1 DEFAULT
MESSAGE
MODE: Default Value
GOOSE ANALOG
MESSAGE
UNITS:
GOOSE ANALOG
MESSAGE
is set to "Default Value".This setting is stored as an IEEE 754 / IEC 60559 floating
L30 Line Current Differential System
Range: FlexLogic™ operand
to identify the source of the command. The setting
operand.
RESET OP (OPERAND)

GOOSE ANALOG INPUT 1(32)
Range: –1000000.000 to 1000000.000 in steps of 0.001
Range: Default Value, Last Known
Range: up to 4 alphanumeric characters
1
Range: 0.000 to 1000000000.000 in steps of 0.001
1 PU:
1.000
ANALOG 1 DEFAULT
5 SETTINGS
5.8.10 RESETTING
5.8.11 IEC 61850 GOOSE ANALOGS
setting.
GE Multilin