User-Programmable Pushbuttons - GE L30 Instruction Manual

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
 USER PUSHBUTTON 1
5
5-50
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL
:
AND
RUN
Enabled=1
OFF
SYSTEM SETUP/
BREAKERS/BREAKER 2/
ON
BREAKER 2 PUSHBUTTON
CONTROL
:
Enabled=1
Figure 5–6: CONTROL PUSHBUTTON LOGIC


USER-PROGRAMMABLE PUSHBUTTONS

PUSHBUTTON 1
FUNCTION: Disabled
PUSHBTN 1 ID TEXT:
MESSAGE
PUSHBTN 1 ON TEXT:
MESSAGE
PUSHBTN 1 OFF TEXT:
MESSAGE
PUSHBTN 1 HOLD:
MESSAGE
0.0 s
PUSHBTN 1 SET:
MESSAGE
Off
PUSHBTN 1 RESET:
MESSAGE
Off
PUSHBTN 1 AUTORST:
MESSAGE
Disabled
PUSHBTN 1 AUTORST
MESSAGE
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
MESSAGE
Off
PUSHBTN 1 LOCAL:
MESSAGE
Off
PUSHBTN 1 DROP-OUT
MESSAGE
TIME: 0.00 s
PUSHBTN 1 LED CTL:
MESSAGE
Off
PUSHBTN 1 MESSAGE:
MESSAGE
Disabled
PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
L30 Line Current Differential System
TIMER
FLEXLOGIC OPERAND
0
CONTROL PUSHBTN 1 ON
100 msec
842010A2.CDR
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1(16)
Range: Self-Reset, Latched, Disabled
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: 0.0 to 10.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0 to 60.00 s in steps of 0.05
Range: FlexLogic™ operand
Range: Disabled, Normal, High Priority
Range: Disabled, Enabled
5 SETTINGS
GE Multilin