GE L30 Instruction Manual page 97

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

3 HARDWARE
Pull the ejector/inserter clips located at the top and at the bottom of each module simultaneously in order to release the
module for removal. Record the original location of the module to help ensure that the same or replacement module is
inserted into the correct slot.
2.
Remove the module cover screw.
3.
Remove the top cover by sliding it towards the rear and then lift it upwards.
4.
Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
5.
Replace the top cover and the cover screw.
6.
Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
Figure 3–41: IEEE C37.94 TIMING SELECTION SWITCH SETTING
GE Multilin
L30 Line Current Differential System
3.3 PILOT CHANNEL COMMUNICATIONS
3
3-39

Advertisement

Table of Contents
loading

Table of Contents