B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 57)
ADDR
REGISTER NAME
601F
87L Inrush Inhibit Level
CT Failure Detector (Read/Write Setting)
6124
CT Fail Function
6125
CT Fail Block
6126
CT Fail Current Source 1
B
6127
CT Fail Current Pickup 1
6128
CT Fail Current Source 2
6129
CT Fail Current Pickup 2
612A
CT Fail Voltage Source
612B
CT Fail Voltage Pickup
612C
CT Fail Pickup Delay
612D
CT Fail Target
612E
CT Fail Events
Autoreclose (Read/Write Setting) (2 modules)
6240
Autoreclose 1 Function
6241
Autoreclose 1 Initiate
6242
Autoreclose 1 Block
6243
Autoreclose 1 Max Number of Shots
6244
Autoreclose 1 Manual Close
6245
Autoreclose 1 Manual Reset from LO
6246
Autoreclose 1 Reset Lockout if Breaker Closed
6247
Autoreclose 1 Reset Lockout On Manual Close
6248
Autoreclose 1 Breaker Closed
6249
Autoreclose 1 Breaker Open
624A
Autoreclose 1 Block Time Upon Manual Close
624B
Autoreclose 1 Dead Time Shot 1
624C
Autoreclose 1 Dead Time Shot 2
624D
Autoreclose 1 Dead Time Shot 3
624E
Autoreclose 1 Dead Time Shot 4
624F
Autoreclose 1 Reset Lockout Delay
6250
Autoreclose 1 Reset Time
6251
Autoreclose 1 Incomplete Sequence Time
6252
Autoreclose 1 Events
6253
Autoreclose 1 Reduce Max 1
6254
Autoreclose 1 Reduce Max 2
6255
Autoreclose 1 Reduce Max 3
6256
Autoreclose 1 Add Delay 1
6257
Autoreclose 1 Delay 1
6258
Autoreclose 1 Add Delay 2
6259
Autoreclose 1 Delay 2
625A
Reserved (4 items)
625E
...Repeated for Autoreclose 2
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence Time Overcurrent 1 Function
6301
Negative Sequence Time Overcurrent 1 Signal Source
6302
Negative Sequence Time Overcurrent 1 Pickup
6303
Negative Sequence Time Overcurrent 1 Curve
6304
Negative Sequence Time Overcurrent 1 Multiplier
6305
Negative Sequence Time Overcurrent 1 Reset
6306
Negative Sequence Time Overcurrent 1 Block
6307
Negative Sequence Time Overcurrent 1 Target
6308
Negative Sequence Time Overcurrent 1 Events
6309
Reserved (7 items)
6310
...Repeated for Negative Sequence Time Overcurrent 2
B-36
RANGE
1 to 40
0 to 1
0 to 65535
0 to 5
0 to 2
0 to 5
0 to 2
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
1 to 4
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 655.35
0 to 65535
0 to 655.35
0 to 0.001
0 to 1
0 to 5
0 to 30
0 to 16
0 to 600
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
%f
0.1
F001
0
---
1
F102
---
1
F300
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F001
---
1
F300
---
1
F300
---
1
F108
---
1
F108
---
1
F300
---
1
F300
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.01
F001
---
1
F300
s
0.01
F001
---
0.001
F001
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
200
0 (Disabled)
0
0 (SRC 1)
2
1 (SRC 2)
2
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
1
0
0
0 (Off)
0 (Off)
0
0
1000
100
200
300
400
6000
6000
500
0 (Disabled)
0
0
0
0
0
0
0
0
0 (Disabled)
0 (SRC 1)
1000
100
0
0 (Self-reset)
0 (Disabled)
0