5 SETTINGS
f) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
 DNP / IEC104
 POINT LISTS
MESSAGE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 BINARY INPUT / MSP
 POINTS
MESSAGE
MESSAGE
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 ANALOG INPUT / MME
 POINTS
MESSAGE
MESSAGE
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the L30 is restarted.
NOTE
GE Multilin


COMMUNICATIONS
DNP / IEC104 POINT LISTS
 BINARY INPUT / MSP
 POINTS
 ANALOG INPUT / MME
 POINTS


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off
L30 Line Current Differential System
5.2 PRODUCT SETUP
Range: see sub-menu below
Range: see sub-menu below
BINARY INPUT / MSP POINTS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand

ANALOG INPUT / MME POINTS
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
5
5-21