5.4 SYSTEM SETUP
PMU 1 CURR TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
SETTINGS
PMU 1 CURR TRIGGER
FUNCTION:
Enabled = 1
PMU 1 CURR TRIG BLK:
Off = 0
SETTINGS
PMU 1 SIGNAL
SOURCE:
IA
IB
IC
j) POWER TRIGGERING

PATH: SETTINGS
SYSTEM SETUP
5
 PMU 1 POWER
 TRIGGER
This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power. The comparator applies a 3% hysteresis.
5-98
SETTINGS
PMU 1 CURR TRIGGER PICKUP:
RUN
I > PICKUP
I > PICKUP
I > PICKUP
Figure 5–35: CURRENT TRIGGER SCHEME LOGIC

PHASOR MEASUREMENT...
PMU 1 POWER TRIGGER
FUNCTION: Disabled
PMU 1 POWER TRIGGER
MESSAGE
ACTIVE: 1.250 pu
PMU 1 POWER TRIGGER
MESSAGE
REACTIVE: 1.250 pu
PMU 1 POWER TRIGGER
MESSAGE
APPARENT: 1.250 pu
PMU 1 POWER TRIGGER
MESSAGE
PKP TIME: 0.10 s
PMU 1 POWER TRIGGER
MESSAGE
DPO TIME: 1.00 s
PMU 1 PWR TRIG BLK:
MESSAGE
Off
PMU 1 POWER TRIGGER
MESSAGE
TARGET: Self-Reset
PMU 1 POWER TRIGGER
MESSAGE
EVENTS: Disabled
L30 Line Current Differential System
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 POWER TRIGGER
PMU 1 ROCOF TRIGGER
SETTING
PMU 1 USER TRIGGER:
Off = 0
SETTINGS
PMU 1 CURR TRIGGER PKP TIME:
PMU 1 CURR TRIGGER DPO TIME:
t
PKP
t
DPO


PMU 1 TRIGGERING
PMU 1 POWER TRIGGER
Range: Enabled, Disabled
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Enabled, Disabled
5 SETTINGS
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
to STAT bits of
the data frame
FLEXLOGIC OPERAND
PMU 1 CURR TRIGGER
847000A1.CDR