System Maintenance

WARNING!
Do not remove the StorEdge Interface cover before five minutes have elapsed after disconnecting all
sources of power, and shutting OFF the inverter and the StorEdge Interface.
WARNING!
Before operating the system, ensure that the power cable and wall outlet have been grounded
properly.
WARNING!
When handling the battery, adhere to all manufacturer safety instructions.
CAUTION!
This unit must be operated under the specified operating conditions as described in the technical
specifications supplied with the unit.
NOTE
The battery used must be NRTL certified.
NOTE
For battery decommissioning and disposal, follow the manufacturer requirements and instructions.
NOTE
The StorEdge Interface is IP65 rated. Unused connectors and glands should be sealed with the
provided seals.
NOTE
The
symbol appears at grounding points on the SolarEdge equipment. This symbol may also be
used in this manual.
System Maintenance
Prior to any system maintenance procedure, disconnect all power sources to the system components, 
as described in this section.
 1.  Turn OFF the inverter ON/OFF switch, and wait until the LCD indicates that the DC voltage is safe 
(<50V), or wait five minutes before continuing to the next step.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five
minutes for the input capacitors of the inverter to discharge.
 2.  Turn OFF the inverter Safety Switch (if applicable).
 3.  Turn OFF the AC switch on the main circuit board.
 4.  If applicable, turn OFF the StorEdge Interface ON/OFF switch.
4
SolarEdge-StorEdge Installation Guide MAN-01-00249-1.2