Battery Troubleshooting
If the Total [Wh] value of the Import meter displays a steady value although the site is consuming power,
check the following:
The meter status LEDs are lit. If the LEDs are all OFF, the meter is not connected to a power source.
l
Check the meter AC connection (10-pin terminal block)
o
Check that the meter breaker is ON
o
There are no loose connections at the 10-pin AC wiring of the meter.
l
The CT black and white cables are correctly connected to the 6-pin connector on the meter:
l
White CT wire is connected to A white
o
Black CT wire is connected to A black
o
CT direction is towards the grid and the green power LEDs are ON. If the LEDs are not green indicating
l
import power - the CTs are reversed.
Battery Troubleshooting
The State line in the battery status screen should display one of the following: Charging, Discharging, Idle,
Off, Init.:
B S N :
X X X X X X X X X
S O E : 8 9 %
T o t a l :
S t a t e :
If Error 186 Battery Comm. Error appears, the battery communication is disconnected. Check the
l
following:
The RS485 control connection to the battery
o
The DIP switches settings on the battery:
o
S2, S6: Left
n
S1, S5: Down
n
S3, S4: Up
n
The ID DIP switches setting on the battery - All should be set to the right (0) position
o
If the state Idle is displayed instead of Charging/Discharging, check the following:
l
The system configuration
o
The DC connection
o
26
Figure 22: Meter with CT
I D : 2 4
W W W W W
P W R :
0 W
0 W h
I d l e
SolarEdge-StorEdge Installation Guide MAN-01-00249-1.2