Storedge Interface Leds - SolarEdge StorEdge Installation Manual

For smart energy management using the storedge interface
Hide thumbs Also See for StorEdge:
Table of Contents

Advertisement

StorEdge Interface LEDs

 
LED location
12V IN (left of the main
board)
12V OUT (right of the
main board)
DC LO (red LED on the
power supply)
DC OK (green LED on
the power supply)
SolarEdge-StorEdge Installation Guide MAN-01-00249-1.2
Functionality
ON -12V (or 13V) is supplied to the
main board
OFF - No power to the main board
ON - 12V (or 13V) is supplied to the
battery (thermal and logic)
OFF - No power supply to the battery
PSU output is low
PSU output is OK
Appendix A: Troubleshooting
Troubleshooting
N/A
Check AC cable is connected to the the
o
PSU.
Check green LED indication on the PSU
o
Check the cable connection between the
o
PSU and the main board
N/A
Check that the 12V IN LED is lit
o
Make sure all Control connections between
o
the inverter and battery are correct
Check the RS485 cable to the inverter and
o
battery
Check the 12V (thermal and logic) voltages
o
to the battery
Check the AC cable connection
N/A
27