Chapter 4: System Configuration
Chapter 4: System Configuration
This chapter describes how to configure your StorEdge system by setting up the communication
between the system components and setting up the required a pplication. To use the StorEdge
applications, the inverter communication board firmware (CPU) version must be 3.xxxx and later. If you
have an inverter with CPU version 2.xxxx, contact SolarEdge support.
Upgrading the Inverter Firmware Version
Upgrade the inverter firmware using the card supplied with the StorEdge Interface.
To upgrade the inverter firmware:
1. Make sure the inverter has been activated using the card supplied with the inverter.
2. If applicable - make sure the ON/OFF switch of the StorEdge Interface is OFF.
3. Make sure the ON/OFF switch of the inverter is OFF.
4. Insert the card into the communication board slot marked "CARD".
5. Turn on t he AC to the StorEdge Interface.
6. Turn on the AC to the inverter.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is
removed.
7. Enter the inverter Setup mode: Press the internal Enter button for 5-10 seconds and release. Enter
the password 12312312.
8. Select Maintenance è SW Upgrade – SD Card. The LCD shows: Running Script... è Done!
If the LCD shows: Script error, contact SolarEdge Support.
18
Figure 21: Inserting the upgrade card
SolarEdge-StorEdge Installation Guide MAN-01-00249-1.2