Connecting the StorEdge Interface to AC
NOTE
The AC is used for auxiliary power only and does not carry high power.
Use a three-wire cable with a cross section of 1-2mm
To connect to AC:
1. Turn OFF the AC power source to be connected to the interface.
2. Remove the interface AC sealing gland.
3. Strip off 5/16" (8mm) of the AC cable insulation and expose two line wires and one grounding wire.
4. Insert two wire ends into the AC terminals (L, N). Fasten the screws with a torque of 0.67 N*m/ 0.5
lb*ft.
5. Connect the grounding wire to the grounding terminal (bus-bar). You can use the bus-bar to connect
the battery grounding cable.
SolarEdge-StorEdge Installation Guide MAN-01-00249-1.2
2
.
Figure 17: AC and grounding connections
Figure 18: StorEdge Interface grounding
Chapter 3: StorEdge Interface Installation
13